![AUTOFLAME Mini Mk8 M.M. Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/autoflame/mini-mk8-m-m/mini-mk8-m-m_installation-and-commissioning-manual_3021294037.webp)
37
0.4 -
25.2
"wg/ 1.1 - 63mBar/ 0.02 - 0.91 PSI (Sensor MM80008)
"wg/ 1.1 - 63mBar/ 0.02 - 0.91 PSI (
感应器
MM80008)
1 - 56
"wg/ 2.5 - 140mBar/ 0.04 - 2.03 PSI (Sensor MM80011)
"wg/ 2.5 - 140mBar/ 0.04 - 2.03 PSI (
感应器
MM80011)
1.9 - 103
"wg/ 4.6 - 356 mBar/ 0.07 - 5.16 PSI (Sensor MM80012)
"wg/ 4.6 - 356 mBar/ 0.07 - 5.16 PSI (
感应器
MM80012)
5.6 - 307
"wg/ 13.9 - 765mBar/ 0.20 - 11.09 PSI (Sensor MM80014)
"wg/ 13.9 - 765mBar/ 0.20 - 11.09 PSI (
感应器
MM80014)
Note:
Only the Mk8 Gas/ Air Pressure Sensors can be used with the Mini Mk8 M.M.
注意:
Mk8
微型控制模块只使用
Mk8
燃气
/
空气压力感应器
134
5
VPS valve opening time:
VPS
(阀门校验系统)阀门开启时间
3 - 20
Seconds.
秒
135
0
Purge time units/ NFPA Post-purge:
吹扫时间单位
/ NFPA
(国家消防协会)后吹扫
0
Purge time in seconds.
吹扫时间以秒计
1
Purge time in minutes.
吹扫时间以分钟计
2
NFPA post purge in seconds.
NFPA
后吹扫以秒计
3
NFPA post purge in minutes.
NFPA
后吹扫以分钟计
Note:
If this Option is set to 2 (NFPA post purge) then Option 118 must be set to a
value of 15 or greater otherwise a lockout warning message will occur. During the
NFPA post purge the servomotors will remain at the position that they were in
before a normal shutdown or lockout (see also Option 67 to 70). The NFPA post
purge will occur under any normal shutdown or lockout at any point in firing.
注意:如果本选项为
2
(
NFPA
后吹扫)那么选项
118
必须设为
15
或者更大值,否
则会出现锁定警告信息。在
NFPA
后吹扫期间的伺服马达将保持它们在正常关机
或者锁定前所处的位置(参见选项
67
到
70
)。在正常关机或所有燃烧锁定情况
下都会执行
NFPA
后吹扫。
136
5.1
Gas pressure switch - offset lower limit:
This Option has two functions:
燃气压力开关
–
下限补偿值:这个选项具有两个功能:
1. Static inlet pressure check - lower limit. This is checked prior to burner firing.
入口静压检查
–
下限值,在燃烧器燃烧之前检查。
2. Run pressure check - lower limit.
运行压力检查
–
下限值
This is an offset from the commissioned value. Refer to Option 131.
这是调试值的补偿值,参见选项
131
。
0.1 - 5
"wg/ 0.2 - 12.4 mBar/ PSI not available (Sensor MM80006)
"wg/ 0.2 - 12.4 mBar/
不采用
PSI (
感应器
MM80006)
0.4 -
25.2
"wg/ 1.1 - 63mBar/ 0.02 - 0.91 PSI (Sensor MM80008)
"wg/ 1.1 - 63mBar/ 0.02 - 0.91 PSI (
感应器
MM80008)
1 - 56
"wg/ 2.5 - 140mBar/ 0.04 - 2.03 PSI (Sensor MM80011)
"wg/ 2.5 - 140mBar/ 0.04 - 2.03 PSI (
感应器
MM80011)
1.9 - 103
"wg/ 4.6 - 356 mBar/ 0.07 - 5.16 PSI (Sensor MM80012)
"wg/ 4.6 - 356 mBar/ 0.07 - 5.16 PSI (
感应器
MM80012)
5.6 - 307
"wg/ 13.9 - 765mBar/ 0.20 - 11.09 PSI (Sensor MM80014)
"wg/ 13.9 - 765mBar/ 0.20 - 11.09 PSI (
感应器
MM80014)
137
5.1
Gas pressure switch - offset upper limit:
This works in the same way as Option 136
but checks the upper limits. This is an offset from the commissioned value. Refer to
Option 131.
燃气压力开关
–
上限补偿值:与选项
136
的原理一样,但设定的是上限补偿值。
参见选项
131
。
0.1 - 5
"wg/ 0.2 - 12.4 mBar/ PSI not available (Sensor MM80006)
"wg/ 0.2 - 12.4 mBar/
不采用
PSI (
感应器
MM80006)
0.4 -
25.2
"wg/ 1.1 - 63mBar/ 0.02 - 0.91 PSI (Sensor MM80008)
"wg/ 1.1 - 63mBar/ 0.02 - 0.91 PSI (
感应器
MM80008)
1 - 56
"wg/ 2.5 - 140mBar/ 0.04 - 2.03 PSI (Sensor MM80011)
"wg/ 2.5 - 140mBar/ 0.04 - 2.03 PSI (
感应器
MM80011)
1.9 - 103
"wg/ 4.6 - 356 mBar/ 0.07 - 5.16 PSI (Sensor MM80012)
"wg/ 4.6 - 356 mBar/ 0.07 - 5.16 PSI (
感应器
MM80012)
5.6 - 307
"wg/ 13.9 - 765mBar/ 0.20 - 11.09 PSI (Sensor MM80014)
Содержание Mini Mk8 M.M.
Страница 1: ...1...
Страница 6: ...6 1 1 Mini Mk8 M M MK8 1 1 1 Fixing Holes and Dimensions...
Страница 7: ...7 1 2 Wiring Schematic...
Страница 8: ...8...
Страница 15: ...15 1 4 Connection Between Mini Mk8 M M and Mk8 E G A Mk8 Mk8 E G A...
Страница 16: ...16 1 5 Connection Between Mini Mk8 M M and Mk7 D T I Mk8 Mk7 D T I...
Страница 17: ...17 1 6 Sequencing Connection Diagram Mk8...
Страница 53: ...53 3 3 3 Servomotors Direction Change...
Страница 85: ...85 Figure 3 7 iv Single Point Change Trim EGA The M M will store the trim values for this position EGA...
Страница 122: ...122 Notes...
Страница 123: ...123...
Страница 124: ...124...