background image

4

LKS 

- S2 24V DC

01

By attaching the drive to a movable
element of the window and connecting
it to a power supply a so-called
“power-operated window” is created
which, according to the Machinery
Directive  2006 / 42 / EG,  represents  a
machine.

Pay attention to possible hazards on
tilting or rotating windows, whose
side closing edges (NSK) are located
at less than 2,5 m installation height 
above the fl oor, under consideration of 
the Control Unit and usage!

n

ote

!

w

aRning

i

ntenDeD

 

uSe

Area of application / Scope of application

This drive is intended for the electromotive opening and
closing of windows in facade or roof areas. 

The main task of this product

, in combination with 

a window and a suitable external control unit, 

is to

evacuate hot smoke and combustion gases in case
of  fi re

, to safe human lives and protect material

assets. Furthermore, with the electromotive operated
window and a suitable external control unit, 

the natural 

ventilation

 of the building can be ensured.

Intended use 

The drive is intended for stationary installation and
electrical connection at the window as part of a building.
The drive is in combination with an external Control Unit
(e.g. from 

a

UMÜlleR

) released for its proper use at a

power-operated window for the following use:
•  Application for natural ventilation
 

  

with an installation height of the drive and

    the bottom side of casement of at least 2,5 m above
  the 

fl 

oor, 

or

 

  

with an opening width at the HSK of the driven

    part of < 200 mm by a simultaneous speed of
    < 15 mm/s at the HSK in closing direction.
•  Application as NSHEV (natural smoke and heat 
  exhaust ventilator(s) in accordance with EN12101-2
  without dual purpose for ventilation.

The need for a risk assessment at the installation site 
due to the reasonably foreseeable misuse.
A risk assessment in accordance with the Machinery 
Directive  2006 / 42 / EG

 for the usage of the power-

operated window 

for natural ventilation is absolutely 

necessary 

under the following conditions:

•  the installation height of the drive and lower edge
  of casement < 2,5 m above the fl oor 
 

and 

one of the following conditions:

•  the opening width at the HSK   is > 200 mm, 

or

•  the closing speed at the HSK   is > 15 mm/s, 

or

•  the opening speed at the HSK  is > 50 mm/s, 

or

•  the closing force at the HSK   is > 150 N
The following fl ow chart can be applied, which also includes 
the protective measures in accordance with EN 60335-2-
103/2016-05.

We as manufacturers are well aware of our duties and 
responsibilities regarding the development, manufactu-
ring and placing of safe window drives on the market and
consistently implement them. Ultimately, however, we have 
no direct infl uence on the usage of our drives. Therefore,
as a precaution, we point out the following:

• The 

constructor or his agent

 (architect, specialist 

 planner) 

are obligated

 

to evaluate the

  hazards to persons

, outgoing from the usage,

  installation position, opening parameters and from the 
  external Control Unit of the power operated window,
 already 

in the planning phase and to establish

  necessary protective measures

• The 

constructor / manufacturer

 of the machine

  “power-operated window” 

must implement

 the 

 planned 

protective measures

 at the installation site 

  or, if not yet established, 

determine them

 by it´s

  own responsibility and detect or 

minimize possible

  remaining risks

.  

P

reliminary

 r

emark

Содержание LKS S2 24V DC

Страница 1: ...according to Machinery Directive 2006 42 EC annex VI LKS S2 24V DC Rack and Pinion Drives for windows Assembly and Commissioning Instructions...

Страница 2: ...a Assembly drive with frame bracket K29 Installation step 4b Assembly drive with adjustable clamping B7 and frame bracket K82 Installation step 4c Assembly drive with adjustable clamping B7 and frame...

Страница 3: ...ng Caution Warning Danger due to electric current Caution Warning Risk of crushing and entrapment during device operati on is provided as a sticker with the drive Attention Warning Risk of damage to d...

Страница 4: ...s NSHEV natural smoke and heat exhaust ventilator s in accordance with EN12101 2 without dual purpose for ventilation The need for a risk assessment at the installation site due to the reasonably fore...

Страница 5: ...witch strips or Motor current monitoring systems internal and external Hold to run switch stops movement at HSK 20 mm at a closing force of 150 N at HSK 20 ZAA 5 Operating element in direct range of v...

Страница 6: ...e electrical supply data see product lable and performance limits see technical data as well as the mounting and installation instructions of the drive must be strictly observed and adhered to Do not...

Страница 7: ...able cable lengths and cross sections shall be selected in accordance with the manufacturer s technical data If necessary the cable types shall be coordinated with the competent local authorities and...

Страница 8: ...e instructed in all important opera ting steps If necessary he must be advised of all remaining risks dangers The end user shall be specifically instructed that no additional forces except pushing and...

Страница 9: ...e and heat exhausting systems SHEV as single drive Internal load dependend cut off switch S2 Options Drillings for front suspension Monitored motion run of 2 drives up to s 300 mm via USKM Order data...

Страница 10: ...formation on the most import ant caracteristics such as manufacturer s address article reference number and name technical caracteristics date of manufacturing with firmware version serial number cert...

Страница 11: ...2200 2400 2600 Abstand Antrieb Band ffnungswinkel 2 1 3 4 5 6 7 8 9 10 1 Hubl nge 100 mm 2 Hubl nge 200 mm 3 Hubl nge 300 mm 4 Hubl nge 400 mm 5 Hubl nge 500 mm 6 Hubl nge 600 mm 7 Hubl nge 700 mm 8...

Страница 12: ...balance The test procedure of drives may only be performed on a non slip and secured mat or a test fixture During the test run the test element must not be interfered with The test my only be conducte...

Страница 13: ...2 FAB 1 2 FAB 1 4 FAB 1 4 FAB Tools required Marker Grains Hammer Screwdriver slotted head cross or Torx size by site conditions Hexagonal wrench size 4 5 Fork wrench for SW13 SW14 Torque wrench Power...

Страница 14: ...et K82 for swivelling suspension Frame bracket K5 for swivelling suspension Adjustable clamping B7 Mounting with K5 or K82 Frame bracket K21K For moving the mounting level from the horizontal to the v...

Страница 15: ...g casement outwards opening Frame assembly HSK View on aluminium window View on PVC window Roof window outwards opening Frame assembly HSK Roof window outwards opening Frame assembly HSK View on alumi...

Страница 16: ...associated bolt 6 of the casement brackets F1 into the eyebolt of LKS Optionally adjust the pressure ball of the casement bracket F1 with grub screw and the spring Adjust casement pressure using of th...

Страница 17: ...linder head screws M6 of the adjustable clamping B7 Slide the adjustable clamping B7 gently on the drive body LKS by hand do not force Screw the cylinder head screws M6 of the adjustable clamping B7 a...

Страница 18: ...e bracket K21K M6 Make sure they are parallel to casement edge Casement bracket center and rack must be in line Determine fastenings for casement bracket F10 6 frame bracket K21K and for frame bracket...

Страница 19: ...arefully clear away drilling swarfs to prevent seals from being damaged Avoid surface scratches for example by using masking tape Secure fasteners against loosening e g by applying removable thread lo...

Страница 20: ...propriate cross section for mounting dimensions see drill holes Installation stepe 3 or project specific documents and drawings Note Screws for mounting on the window are to be provided by the custome...

Страница 21: ...s s 300 mm max 2 5 A IP 54 0 C 70 C 110 x 110 x 66 mm Motion monitoring up to 3 drives 2 sequential controls DIP switches for settings Connection terminals 2 5 mm 24V Installation step 6 Electric conn...

Страница 22: ...he homepage of Firm aUM lleR aUMatIc GmbH www aumueller gmbh de Safety CheCk anD teSt Run Formula to calculate the required wire cross section of a supply line Calculation example Available data cut o...

Страница 23: ...ear or damages of cables and fastening elements must be performed During maintenance contaminations must be removed from the drive Fastenings and clamping screws must be checked for tightness Test run...

Страница 24: ...or delivered material is twelve months Warranty and liability claims for personal injuries or material damages are excluded if caused by one or more of the following No proper incoming goods inspectio...

Страница 25: ...25 LKS S2 24V DC Notes 08...