21
LKS
- S2 24V DC
e
leCtriC
C
onneCtion
06
F10.6
LKS
±7
8
1
7
2
M8
(SW13)
Adjust casement pressure by unfastening the drive
LKS
from the casement bracket
Fxx
.
Release the nut M8 (SW13)
and turn the eyebolt
in or out - until the casement pressure fits.
Reattach the drive
LKS
to the casement bracket
Fxx
.
Control module: USKM
Order number:
Application:
Rated voltage:
Close circiut current:
Connections:
Rated current per drive:
Protection rating:
Ambient temperature range:
Surface mount. plastic housing:
512140
with 3 outputs and individual
settuble cut-off current,
monitored motion run,
delayed sequence control.
24V DC (19 V ... 28 V)
< 50 mA
max. 3 drives; s < 300 mm
max. 2,5 A
IP 54
0 °C ... +70 °C
110 x 110 x 66 mm
Motion-monitoring up to 3 drives,
2 sequential controls
DIP switches:
for settings.
Connection terminals:
2,5 mm²
24V
I
nstallatIon
step
6:
e
leCtRiC
ConneCtion
I
nstallatIon
step
5:
P
oSSibility
of
aDjuStment
foR
the
CaSement
PReSSuRe
Drives must be switched by the controller to
the opposite direction (pole reversed) when
switched off at overload.
Connection assignment
LKS
S2
= with internal load dependend cut-off switch
s2
!
BN
BU
Direction of travel
OPEN
CLOSE
polarity reversal
+
+
-
-
Wire colour coding
Colour
DIN IEC 757
brown
BN
blue
BU
Make sure when establishing the connection
that there is no voltage at the terminals!
Unused wires must be safely insulated!
The running direction of the drive may be changed by
interchanging (polarity reversal) the wires
„BN – (brown)“
-
„BU – (blue)“
.
LKS
BN
BU
07