Features and functions of actuator controls

Switch-off mode adjustable:

-

Limit or torque seating for end position OPEN and end position CLOSED

Torque monitoring across the whole travel

Torque by-pass

Programmable EMERGENCY behaviour

-

Digital input low active

-

Reaction can be selected: Stop, run to end position CLOSED, run to end position
OPEN

Positioner (for modulating actuators):

-

Position setpoint via analogue input E1 = 0/4 – 20 mA

-

Programmable behaviour on loss of signal

-

Automatic adaptation of the dead band (adaptive behaviour selectable)

-

Switch-over between OPEN - CLOSE control (REMOTE OPEN-CLOSE) and setpoint
control (REMOTE SETPOINT) via digital MODE input

Functions

Plug/socket connector with crimp connection

Standard:

Electrical connection

AUMA plug/socket connector with screw-type connection

Option:

Refer to name plate

Wiring diagram

Service conditions

Any position

Mounting position

 2 000 m above sea level

> 2,000 m above sea level on request

Installation altitude

Refer to name plate
Standard: –25 °C to +70 °C

Ambient temperature

Up to 100 % relative humidity across the entire permissible temperature range

Humidity

Refer to name plate
IP68
According to AUMA definition, enclosure protection IP68 meets the following requirements:

Depth of water: maximum 8 m head of water

Duration of continuous immersion in water: Max. 96 hours

Up to 10 operations during continuous immersion

Modulating duty is not possible during continuous immersion

Enclosure protection according
to EN 60529

Pollution degree 4 (when closed) according to IEC 61800-5-1

Pollution degree

2 g, from 10 to 200 Hz
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength
may not be derived from this.

Vibration resistance according
to IEC 60068-2-6

Environmental categories D, G, EMC2

GL approval

Suitable for use in areas with high salinity, almost permanent con-
densation, and high pollution.

KS:

Standard:

Corrosion protection

Suitable for use in areas with extremely high salinity, permanent
condensation, and high pollution.

KX:

Option:

Standard: Two-component iron-mica combination

Finish coating

AUMA silver-grey (similar to RAL 7037)

Standard:

Colour

Available colours on request

Option:

20,000 operating cycles OPEN - CLOSE - OPEN
An operating cycle is based on an operation from CLOSED to OPEN and
back to CLOSED

Open-close duty:

Lifetime

5 million modulating steps
The lifetime depends on the load and the number of starts. A high starting
frequency will rarely improve the modulating accuracy. To reach the longest
possible maintenance and fault-free operating time, the number of starts
per hour chosen should be as low as permissible for the process.

Modulating duty:

Further information

Electromagnetic Compatibility (EMC): (2004/108/EC)
Low Voltage Directive: (2006/95/EC)
Machinery Directive: (2006/42/EC)

EU Directives

46

 SVC 05.1 – SVC 07.5/ SVCR 05.1 – SVCR 07.5

Technical data Globe valve actuator

Содержание SVC 05.1

Страница 1: ...Control Parallel Profibus DP Modbus RTU Globe valve actuators SVC 05 1 SVC 07 5 SVCR 05 1 SVCR 07 5 with integral actuator controls Assembly operation commissioning Operation instructions...

Страница 2: ...22 option 5 1 4 Warnings and notes 6 1 5 References and symbols 7 2 Identification 7 2 1 Name plate 8 2 2 Short description 10 3 Transport storage and packaging 10 3 1 Transport 10 3 2 Storage 10 3 3...

Страница 3: ...ection set again via local controls 35 10 2 1 End position CLOSED set again 35 10 2 2 End position OPEN set again 36 10 3 Switch compartment open 36 10 4 Potentiometer setting 38 10 5 Mechanical posit...

Страница 4: ...e valve or the installation The manufacturer will not be held liable for any consequential damage Such risk lies entirely with the user Operation Prerequisites for safe and smooth operation Correct tr...

Страница 5: ...ng the requirements of the duty type and the technical data are prerequis ites for compliance with the maximum surface temperature of devices The connectors may only be connected or disconnected when...

Страница 6: ...The following references and symbols are used in these instructions Information The term Information preceding the text indicates important notes and information Symbol for CLOSED valve closed Symbol...

Страница 7: ...f manufacturer 3 Type designation 4 Order number 5 Actuator serial number 6 Speed 7 Torque range 8 Current type mains voltage mains frequency 9 Electric power motor 10 Wiring diagram number 11 Control...

Страница 8: ...ntrol via parallel interface at 24 V DC control voltage 0 4 20 mA Control via parallel interface via analogue input 0 4 20 mA Data Matrix code When registered as authorised user you may use the AUMA S...

Страница 9: ...The connection between computer and the integral actuator controls is made using a service cable 9 SVC 05 1 SVC 07 5 SVCR 05 1 SVCR 07 5 Identification...

Страница 10: ...months the following points must be observed in addition 1 Prior to storage Protect uncoated surfaces in particular the output drive parts and mounting surface with long term corrosion protection agen...

Страница 11: ...either in position CLOSED or position OPEN The mechanical position indicator supplies information on the set position If the actuator position was not modified and agrees with the valve position the...

Страница 12: ...s 1 Bore with keyway 2 Square bore 3 Bore with two flats 4 Valve shaft 4 3 2 1 Mounting with coupling Condition Valve and actuator are in the same end position Figure 6 Coupling fitting dimensions 1 C...

Страница 13: ...recess and that the flanges are in complete contact 6 If flange bores do not match thread 6 1 Slightly rotate handwheel until bores line up 6 2 If required shift actuator position by one tooth on the...

Страница 14: ...following values 15 A 250 V at a maximum mains current of 5 000 A AC Use appropriate insulation monitors when working in power installations for example an insulation monitor measuring the pulse code...

Страница 15: ...nstallation use UV resistant cables The cross sectional area of every protective earthing conductor which does not form not part of the supply cable or the cable enclosure shall in any case not be les...

Страница 16: ...nufacturer Upon request AUMA provide suitable connection sets For further information refer to separate Technical data Connector Use in Ex zone 22 is only possible with straight single connectors and...

Страница 17: ...ec tion Observe permissible cross sections of connectors used Use suitable crimping tools to connect wires For screw type connectors e g Phoenix 4 arbor crimping pliers For bayonet connectors e g Cann...

Страница 18: ...5 4 Connection with AUMA plug socket connector Figure 12 Connection with AUMA plug socket connector Cross sections AUMA plug socket connector Power terminals U1 V1 W1 U2 V2 W2 max 6 mm flexible 10 mm...

Страница 19: ...ires 3 For flexible cables Use end sleeves according to DIN 46228 4 Connect cables according to order related wiring diagram In case of a fault Hazardous voltage while protective earth conductor is NO...

Страница 20: ...1 and fasten with screws 4 2 Clean sealing faces of cover 1 and housing 3 Check whether O ring 3 is in good condition replace if damaged 4 Apply a thin film of non acidic grease e g petroleum jelly t...

Страница 21: ...racket 2 Local controls 3 Phoenix connector with connecting cable Observe prior to connec tion Permissible length of connecting cables max 30 m We recommend AUMA cable set K008 218 5 m A retrofit kit...

Страница 22: ...ellow blue Table 4 Indication light 1 default setting Description Signification Colour state Actuator is in end position OPEN OPEN illuminated in green Stroke between selected end positions OPEN CLOSE...

Страница 23: ...Description Signification Colour state Setting mode for end position setting is active Set end position blinking in blue 5 Hz 23 SVC 05 1 SVC 07 5 SVCR 05 1 SVCR 07 5 Indications...

Страница 24: ...ation of output contacts in wiring diagram Signal DOUT 1 End position CLOSED K 1 End position CLOSED Signal DOUT 2 End position OPEN K 2 End position OPEN Signal DOUT 3 Fault K 3 Fault Signal DOUT 4 S...

Страница 25: ...wheel counterclockwise Drive shaft valve turns counterclockwise in direction OPEN Information Turning the handwheel during motor operation extends or reduces the operating time depending on the direct...

Страница 26: ...chapter It is possible to temporarily for one operation command activate self retaining by means of the push buttons Press and hold down push buttons OPEN 1 or CLOSE 3 for more than 3 seconds During...

Страница 27: ...e g 0 4 20 mA EMERGENCY operation An EMERGENCY operation is initiated by a signal at the EMERGENCY input The actuator moves to a predefined EMERGENCY position i e end position OPEN or end position CL...

Страница 28: ...accessories By connecting a PC laptop or PDA Also refer to AUMA CDT software accessories chapter Please also refer to AUMA CDT software accessories chapter for further settings 9 1 Cover to controls...

Страница 29: ...with the consent of the valve manufacturer Setting via switches Condition Switch S5 in position OFF hardware mode Figure 23 Switches for type of seating S9 End position OPEN S10 End position CLOSED T...

Страница 30: ...irection CLOSE Default value depending on the order Setting range in 8 steps refer to tables linear from 40 100 of the maximum tripping torque Table 8 Tripping torques Nm Switch steps SVC SVCR 07 5 SV...

Страница 31: ...ftware parameters AUMA CDT The motor speed can be modified via the software parameters described hereafter Contrary to output speed setting using switch S8 setting via software parameters offers the f...

Страница 32: ...eed via parameter Speed LOCAL Speed REMOTE 4 20 mA 0 20 mA 1 6 133 4 0 0 0 0 0 2 2 176 4 3 0 4 2 0 3 2 256 4 9 1 2 6 0 4 320 5 4 1 8 9 0 5 6 448 6 4 3 0 15 0 8 640 7 8 4 8 24 0 11 880 9 6 7 1 35 0 16...

Страница 33: ...film of non acidic grease e g petroleum jelly to the seal and insert it correctly 5 Place cover 1 6 Fasten screws evenly crosswise 33 SVC 05 1 SVC 07 5 SVCR 05 1 SVCR 07 5 Commissioning basic setting...

Страница 34: ...on OPEN the indication lights go out after travelling into opposite direction The end position detection is set incorrectly if the actuator comes to a standstill before reaching the end position the l...

Страница 35: ...setting is not permissible while the indication light is blinking in red potentiometer setting must be performed in a first step also refer to Potentiometer setting chapter Once this procedure is com...

Страница 36: ...d again either via push buttons 1 3 in operation mode Local or from Remote deactivate operation mode Local Deactivate operation mode Local 5 Hold down push button 2 for approx 3 seconds until blue ind...

Страница 37: ...ter by means of the setting screw 1 results in modification of the end position detection Only set potentiometer if the end position detection cannot be set Fault signal Actuator is outside the permis...

Страница 38: ...OPEN 4 Hold lower indicator disc in position and turn upper disc with symbol OPEN until it is in alignment with the mark on the cover 5 Move valve to end position CLOSED again 6 Check settings If the...

Страница 39: ...acidic grease e g petroleum jelly to the O ring and insert it correctly 5 Place cover 1 on switch compartment 6 Fasten screws 2 evenly crosswise 39 SVC 05 1 SVC 07 5 SVCR 05 1 SVCR 07 5 Commissioning...

Страница 40: ...Software mode Refer to Settings via hardware switches or via software chapter Switches and software parameters are set to the same values upon delivery factory settings Further settings via AUMA CDT A...

Страница 41: ...ite direction Fault indication 1 1 blink Thermal fault motor protection tripped Cool down wait Fault indication 2 2 blinks Signal loss of analogue input 4 20 mA Fault indication 3 3 blinks Operation m...

Страница 42: ...le when removing the cover to the controls The fuse cannot be replaced Only by replacing the entire power board can the fuse be exchanged Hazardous voltage Risk of electric shock Disconnect device fro...

Страница 43: ...ate leaks and repair dry device correctly and check for proper function 13 2 Maintenance Maintenance intervals The maintenance intervals depend on load and application conditions having a major influe...

Страница 44: ...lating torque load The type of duty must not be exceeded Variable speed brushless motor Motor F tropicalized Insulation class PTC thermistors according to DIN 44081 Motor protection Yes Self locking V...

Страница 45: ...mbination with positioner option OPEN EMERGENCY CLOSE MODE in combination with positioner option Assignment for modulating actuators OPEN STOP CLOSE MODE standard OPEN EMERGENCY CLOSE MODE Analogue in...

Страница 46: ...tions during continuous immersion Modulating duty is not possible during continuous immersion Enclosure protection according to EN 60529 Pollution degree 4 when closed according to IEC 61800 5 1 Pollu...

Страница 47: ...15 Spare parts 15 1 Globe valve actuator SVC 05 1 SVC 07 5 SVCR 05 1 SVCR 07 5 47 SVC 05 1 SVC 07 5 SVCR 05 1 SVCR 07 5 Spare parts...

Страница 48: ...sembly Power supply unit switchgear 006 0 Logic board 009 0 Sub as sembly Wire for protective earth 058 0 Sub as sembly Cover 500 0 Sub as sembly Socket carrier complete with sockets 501 0 Sub as sem...

Страница 49: ...16 Certificates 16 1 Declaration of Incorporation and EC Declaration of Conformity 49 SVC 05 1 SVC 07 5 SVCR 05 1 SVCR 07 5 Certificates...

Страница 50: ...50 SVC 05 1 SVC 07 5 SVCR 05 1 SVCR 07 5...

Страница 51: ...51 SVC 05 1 SVC 07 5 SVCR 05 1 SVCR 07 5...

Страница 52: ...detection verific ation 34 End postion detection 44 F Failure behaviour 40 Fault indications 41 Finish coating 46 Flange size 8 Fuses 42 G GL approval 46 Ground connection 20 H Handwheel 11 Humidity...

Страница 53: ...ng 43 Setpoint control Remote SETPOINT 26 Settings for controls 28 Short circuit protection 14 Signals 24 Signals analogue 24 Size 8 Software 28 40 Spare parts 47 Standards 4 Storage 10 Supply network...

Страница 54: ...www apis centar com Fabo Kereskedelmi s Szolg ltat Kft HU 8800 Nagykanizsa Tel 36 93 324 666 auma fabo hu www fabo hu Falkinn HF IS 108 Reykjavik Tel 00354 540 7000 os falkinn is www falkinn is AUMA...

Страница 55: ...80 2839 4656 info auma co in www auma co in ITG Iranians Torque Generator IR 13998 34411 Teheran 982144545654 info itg co ir Trans Jordan Electro Mechanical Supplies JO 11133 Amman Tel 962 6 5332020...

Страница 56: ...r GmbH Co KG P O Box 1362 DE 79373 Muellheim Tel 49 7631 809 0 Fax 49 7631 809 1250 riester auma com www auma com Y005 019 003 en 1 15 For detailed information on AUMA products refer to the Internet w...

Отзывы: