Features and functions of actuator controls
●
Switch-off mode adjustable:
-
Limit or torque seating for end position OPEN and end position CLOSED
●
Torque monitoring across the whole travel
●
Torque by-pass
●
Programmable EMERGENCY behaviour
-
Digital input low active
-
Reaction can be selected: Stop, run to end position CLOSED, run to end position
OPEN
●
Positioner (for modulating actuators):
-
Position setpoint via analogue input E1 = 0/4 – 20 mA
-
Programmable behaviour on loss of signal
-
Automatic adaptation of the dead band (adaptive behaviour selectable)
-
Switch-over between OPEN - CLOSE control (REMOTE OPEN-CLOSE) and setpoint
control (REMOTE SETPOINT) via digital MODE input
Functions
Plug/socket connector with crimp connection
Standard:
Electrical connection
AUMA plug/socket connector with screw-type connection
Option:
Refer to name plate
Wiring diagram
Service conditions
Any position
Mounting position
≤
2 000 m above sea level
> 2,000 m above sea level on request
Installation altitude
Refer to name plate
Standard: –25 °C to +70 °C
Ambient temperature
Up to 100 % relative humidity across the entire permissible temperature range
Humidity
Refer to name plate
IP68
According to AUMA definition, enclosure protection IP68 meets the following requirements:
●
Depth of water: maximum 8 m head of water
●
Duration of continuous immersion in water: Max. 96 hours
●
Up to 10 operations during continuous immersion
●
Modulating duty is not possible during continuous immersion
Enclosure protection according
to EN 60529
Pollution degree 4 (when closed) according to IEC 61800-5-1
Pollution degree
2 g, from 10 to 200 Hz
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength
may not be derived from this.
Vibration resistance according
to IEC 60068-2-6
Environmental categories D, G, EMC2
GL approval
Suitable for use in areas with high salinity, almost permanent con-
densation, and high pollution.
KS:
Standard:
Corrosion protection
Suitable for use in areas with extremely high salinity, permanent
condensation, and high pollution.
KX:
Option:
Standard: Two-component iron-mica combination
Finish coating
AUMA silver-grey (similar to RAL 7037)
Standard:
Colour
Available colours on request
Option:
20,000 operating cycles OPEN - CLOSE - OPEN
An operating cycle is based on an operation from CLOSED to OPEN and
back to CLOSED
Open-close duty:
Lifetime
5 million modulating steps
The lifetime depends on the load and the number of starts. A high starting
frequency will rarely improve the modulating accuracy. To reach the longest
possible maintenance and fault-free operating time, the number of starts
per hour chosen should be as low as permissible for the process.
Modulating duty:
Further information
Electromagnetic Compatibility (EMC): (2004/108/EC)
Low Voltage Directive: (2006/95/EC)
Machinery Directive: (2006/42/EC)
EU Directives
46
SVC 05.1 – SVC 07.5/ SVCR 05.1 – SVCR 07.5
Technical data Globe valve actuator