10.2.1.
End position CLOSED: set again
Activate setting mode "end position setting":
1.
Press push button [2] – hold down and press push buttons [1] and [3] at the
same time.
➥
Now, the right indication light is blinking faster (5 Hz).
Set end position CLOSED:
2.
Use crank handle/handwheel or push button [3] for running the actuator to end
position CLOSED. (Actuator runs at reduced output speed in setting mode.)
Information: If the red indication light is blinking (6 blinks), the actuator is
outside the permissible setting range (0 – 100 %).
During electrical operation via push buttons, the actuator stops and cannot
resume operation (up to valve end position). Since end position setting is not
permissible while the indication light is blinking in red, potentiometer setting
must be performed in a first step (also refer to <Potentiometer setting> chapter).
Once this procedure is complete, setting can be resumed and the end position
can be set again as described .
3.
Press push button [2] – hold it down and press push button [3]. Hold both push
buttons down until the right indication light is blinking alternately in yellow and
blue (default).
➥
If the right indication light is blinking in yellow/blue, end position CLOSED setting
is complete.
10.2.2.
End position OPEN: set again
Activate setting mode "end position setting":
1.
Press push button [2] – hold down and press push buttons [1] and [3] at the
same time.
➥
Now, the right indication light is blinking faster (5 Hz).
35
SVC 05.1 – SVC 07.5/ SVCR 05.1 – SVCR 07.5