Hazardous voltage!
Risk of electric shock.
→
Disconnect device from the mains before opening.
1.
Loosen screws [2] and remove cover [1].
2.
Loosen screws [4] and remove socket carrier [5] from cover [1].
3.
Insert cable glands [8] suitable for connecting cables.
➥
The enclosure protection IP… stated on the name plate is only ensured if suit-
able cable glands are used.
4.
Seal unused cable entries [6] with suitable blanking plugs [7].
5.
Insert the cables into the cable glands [8].
5.4.2.
Cable connection
✔
Observe permissible cross sections.
1.
Remove cable sheathing.
2.
Strip wires.
3.
For flexible cables: Use end sleeves according to DIN 46228.
4.
Connect cables according to order-related wiring diagram.
In case of a fault: Hazardous voltage while protective earth conductor is NOT
connected!
Risk of electric shock.
→
Connect all protective earth conductors.
→
Connect PE connection to external protective earth conductor of connecting
cables.
→
Start running the device only after having connected the protective earth con-
ductor.
5.
Tighten PE conductors firmly to PE connection using ring lugs (flexible cables)
or loops (rigid cables).
Figure 14: PE connection
[1]
Socket carrier
[2]
Screw
[3]
Washer
[4]
Lock washer
[5]
Protective earth with ring lugs/loops
[6]
PE connection, symbol:
19
SVC 05.1 – SVC 07.5/ SVCR 05.1 – SVCR 07.5
Electrical connection