In case of a fault: Hazardous voltage while protective earth conductor is NOT
connected!
Risk of electric shock.
→
Connect all protective earth conductors.
→
Connect PE connection to external protective earth conductor of connecting
cables.
→
Start running the device only after having connected the protective earth con-
ductor.
2.
Connect protective earth conductor according to wiring diagram, symbol:
.
5.4.
Connection with AUMA plug/socket connector
Figure 12: Connection with AUMA plug/socket connector
Cross sections AUMA plug/socket connector:
●
Power terminals (U1, V1, W1, U2, V2, W2): max. 6 mm² flexible/10 mm² solid
●
PE connection : max. 6 mm² flexible/10 mm² solid
●
Control contacts (1 to 50): max. 2.5 mm²
5.4.1.
Terminal compartment: open
Figure 13: Connection AUMA plug/socket connector, version S
[1]
Cover
[2]
Screws for cover
[3]
O-ring
[4]
Screws for socket carrier
[5]
Socket carrier
[6]
Cable entry
[7]
Blanking plugs
[8]
Cable gland (not included in delivery)
18
SVC 05.1 – SVC 07.5/ SVCR 05.1 – SVCR 07.5
Electrical connection