Description of parameters:
Speed LOCAL
Output speed for operation via local controls (operation mode Local); Setting range:
linear between 0 – 100 % (0 % = min. motor speed, 100 % = max. motor speed);
Default value = 50.0 %
Speed REMOTE
Output speed in operation mode Remote for setting the
Speed I/O interface
=
Internal
parameter; Setting range: linear between 0 – 100 % (0 % = min. motor speed, 100
% = max. motor speed); Default value = 50.0 %
Speed I/O interface
=
External
In operation mode Remote, the output speed is defined via analogue input AIN (0/4
– 20 mA).
=
Internal
In operation mode Remote, the output speed is not defined via analogue input AIN
1 but via the
Speed REMOTE
software parameter.
Table 10: Example values of type range settings SVC/SVCR 05.1/07.1
Output speed
Output drive
[rpm]
Output speed
Motor
[rpm]
Output speed via AIN1
(
Speed I/O interface
=
External
)
Output speed via parameter:
Speed LOCAL
Speed REMOTE
4 – 20 mA
0 – 20 mA
1.6
133
4.0
0.0
0.0 %
2.2
176
4.3
0.4
2.0 %
3.2
256
4.9
1.2
6.0 %
4
320
5.4
1.8
9.0 %
5.6
448
6.4
3.0
15.0 %
8
640
7.8
4.8
24.0 %
11
880
9.6
7.1
35.0 %
16
1280
12.7
10.8
54.0 %
22
1760
16.3
15.4
77.0 %
28.1
2250
20.0
20.0
100.0 %
Table 11: Example values of type range settings SVC/SVCR 07.5
Output speed
Output drive
[rpm]
Output speed
Motor
[rpm]
Output speed via AIN1
(
Speed I/O interface
=
External
)
Output speed via parameter:
Speed LOCAL
Speed REMOTE
4 – 20 mA
0 – 20 mA
0.6
133
4.0
0.0
0.0 %
0.8
186
4.4
0.5
2.0 %
1.1
255
4.9
1.2
6.0 %
1.6
371
5.8
2.3
11.0 %
2.2
510
6.9
3.6
18.0 %
3.2
742
8.6
5.8
29.0 %
4.0
928
10.0
7.5
38.0 %
5.6
1,299
12.8
11.0
55.0 %
8.0
1,856
17.0
16.3
81.0 %
9.7
2,250
20.0
20.0
100.0 %
9.6.
Cover to controls: close
1.
Clean sealing faces of housing and cover.
2.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the sealing faces.
3.
Check whether seal is in good condition, replace seal if damaged.
32
SVC 05.1 – SVC 07.5/ SVCR 05.1 – SVCR 07.5
Commissioning (basic settings of controls)