7.
Signals
7.1.
Output contacts (binary)
The integral controls are equipped with 4 semiconductor output contacts.
Rated power: 24 V DC, 1A
Switches: 1 NO (standard)
Default values:
Designation of output contact in AUMA CDT soft-
ware
Designation of output contacts in
wiring diagram
Signal DOUT 1
=
End position CLOSED
K 1 = End position CLOSED
Signal DOUT 2
=
End position OPEN
K 2 = End position OPEN
Signal DOUT 3
=
Fault
K 3 = Fault
Signal DOUT 4
=
Selector sw. REMOTE
K 4 = (Selector switch) REMOTE
7.2.
Analogue signals
— Option —
Valve position
Signal: E2 = 0/4 – 20 mA (galvanically isolated)
Designation in the wiring diagram:
ANOUT1 (position)
24
SVC 05.1 – SVC 07.5/ SVCR 05.1 – SVCR 07.5
Signals