Commissioning (basic settings of controls)
To prevent valve damage and disturbances during commissioning, the basic settings
of controls must be verified prior to electrical actuator operation (motor operation)
and adapted in compliance with the requirements of both valve and application.
Basic settings of controls comprise:
●
Setting the type of seating
●
Setting the torque switches
●
Setting the output speed
To perform basic settings, proceed as follows:
1.
via switches (directly at the device);
For switch setting, open controls cover.
2.
via AUMA CDT software (accessories);
By connecting a PC, laptop or PDA.
Also refer to <AUMA CDT software (accessories)> chapter.
Please also refer to <AUMA CDT software (accessories)> chapter for further settings.
9.1.
Cover to controls: open
The cover to the integral controls must be opened to perform the following settings
(options).
Hazardous voltage!
Risk of electric shock.
→
Disconnect device from the mains before opening.
→
Loosen 4 screws and remove cover [1] to controls.
9.2.
Setting via hardware (switches) or via software
The switch [S5] position determines whether the hardware settings (switches) or the
software settings (via AUMA CDT software) are currently active.
Figure 22: Switch [S5] = Hardware/software mode
28
SVC 05.1 – SVC 07.5/ SVCR 05.1 – SVCR 07.5
Commissioning (basic settings of controls)