4.2 Diagnostic mode
This mode is used to mainly diagnose the control module and its configurations. This
device diagnostic option can be used to see the Device information, Bluetooth
information, Absolute encoder value, RTC settings, MWG and profibus CAN details,
Profibus details, Factory reset, Thermal proof test as shown in the below flow chart to
Enter Diagnostic Mode press "STOP " key for approximately 3 seconds when the actuator
is in the off mode as shown below.
Step 1
: Keep the selector switch in OFF position
Step 2
: Press "STOP" keys (together) approximately 3 seconds
Step 3
: Press the STOP key on the display of “Diagnostic Mode” as shown below.
From Diagnostic mode you can get the following values: The software version installed,
the raw RTC and POT values etc. can be checked here. One can give commands and
check if these values increase/decrease accordingly. The RTC reading can be verified
and checked if it is correct. A factory reset to set the system into default settings
according to the customer specifications can be carried out. Besides this, there is an
option of Factory settings in the module only under the scope of AUMA India service
engineer that has several software configurable options.
Weather proof actuators with 3.XMP-SIL &
Data logging
Содержание SA3-SA100
Страница 18: ...18 Weather proof actuators with 3 XMP SIL Data logging...
Страница 19: ...19 Weather proof actuators with 3 XMP SIL Data logging...
Страница 20: ...20 Weather proof actuators with 3 XMP SIL Data logging...
Страница 21: ...21 Weather proof actuators with 3 XMP SIL Data logging...
Страница 22: ...22 Weather proof actuators with 3 XMP SIL Data logging...
Страница 23: ...23 Weather proof actuators with 3 XMP SIL Data logging...
Страница 25: ...25 Weather proof actuators with 3 XMP SIL Data logging...
Страница 28: ...28 Weather proof actuators with 3 XMP SIL Data logging...
Страница 31: ...31 Weather proof actuators with 3 XMP SIL Data logging...
Страница 41: ...41 Wiring Diagram for SIL with Pro bus DP Weather proof actuators with 3 XMP SIL Data logging...
Страница 42: ...42 Wiring Diagram for SIL without Pro bus DP Weather proof actuators with 3 XMP SIL Data logging...
Страница 43: ...43 Wiring Diagram for SIL without Pro bus DP Weather proof actuators with 3 XMP SIL Data logging...
Страница 44: ...44 SIL Certi cate Weather proof actuators with 3 XMP SIL Data logging...
Страница 46: ...46 Weather proof actuators with 3 XMP SIL Data logging...
Страница 47: ...47 Weather proof actuators with 3 XMP SIL Data logging...