F 32
Code
Description
Recommended Troubleshooting of Lockout
Codes
Note
78
Demand Lost in Run
1.
Check wiring and correct any possible errors.
2.
If previous steps are correct and fault persists, replace the
module.
H
79
Outlet high limit
1.
Check wiring and correct any possible errors.
2.
Replace the Outlet high limit.
3.
If previous steps are correct and fault persists, replace the
module.
H or L
80
DHW high limit
1.
Check wiring and correct any possible errors.
2.
Replace the DHW high limit.
3.
If previous steps are correct and fault persists, replace the
module.
H or L
81
Delta T limit
1.
Check Inlet and Outlet sensors and pump circuits for proper
operation.
2.
Recheck the Delta T Limit to con rm proper setting.
3.
If previous steps are correct and fault persists, replace the
module.
H or L
82
Stack limit
1.
Check wiring and correct any possible errors.
2.
Replace the Stack high limit.
3.
If previous steps are correct and fault persists, replace the
module.
H or L
83-90
RESERVED
H or L
Sensor Faults
91
Inlet sensor fault
1.
Check wiring and correct any possible errors.
2.
Replace the Inlet sensor.
3.
If previous steps are correct and fault persists, replace the
module.
H
92
Outlet sensor fault
1.
Check wiring and correct any possible errors.
2.
Replace the Outlet sensor.
3.
If previous steps are correct and fault persists, replace the
module.
H
93
DHW sensor fault
1.
Check wiring and correct any possible errors.
2.
Replace the DHW sensor.
3.
If previous steps are correct and fault persists, replace the
module.
H
94
Header sensor fault
1.
Check wiring and correct any possible errors.
2.
Replace the header sensor.
3.
If previous steps are correct and fault persists, replace the
module.
H
95
Stack sensor fault
1.
Check wiring and correct any possible errors.
2.
Replace the stack sensor.
3.
If previous steps are correct and fault persists, replace the
module.
H
96
Outdoor sensor fault
1.
Check wiring and correct any possible errors.
2.
Replace the outdoor sensor.
3.
If previous steps are correct and fault persists, replace the
module.
H
97
Internal Fault: A2D mismatch.
Internal Fault.
1. Reset
Module.
2.
If fault repeats, replace module.
L
98
Internal Fault: Exceeded VSNSR voltage
L
99
Internal Fault: Exceeded 28V voltage tolerance
L
100
Pressure Sensor Fault
1.
Verify the Pressure Sensor is a 4-20ma source.
2.
Check wiring and correct any possible errors.
3.
Test Pressure Sensor for correct operation.
4.
Replace the pressure sensor.
5.
If previous steps are correct and fault persists, replace the
module.
H
101
-104
RESERVED
Flame Operation Faults