Gases may form a white vapor plume in the winter.
The plume could allow hazardous ue gas in through
an open window or obstruct a window view if the
termination is installed near windows.
•
Prevailing winds, in combination with below freezing
temperatures, can cause freezing of condensate and
water/ice build up on building, plants or roofs.
•
The bottom of the vent terminal and air intake shall
be located at least 12” above grade, including normal
snow line.
•
Non-insulated single wall Category IV metal vent pipe
shall not be used outdoors in cold climates for vent-
ing gas– red equipment without insulation.
•
Through-the-wall vents for Category IV appliances
shall not terminate over public walkways or over an
area where condensate or vapor could be detrimental
to the operation of regulators, relief valves, or other
equipment.
•
Locate and guard vent termination to prevent acci-
dental contact by people or pets.
•
Do not terminate vent in a window well, stairwell,
alcove, courtyard or other recessed area.
•
Do not terminate above any door, window, or gravity
air intake. Condensate can freeze, causing ice forma-
tions.
•
Locate or guard vent to prevent condensate from
damaging exterior nishes. Use a rust resistant sheet
metal backing plate against brick masonry surfaces.
•
Do not extend exposed vent pipe outside of building
beyond minimum distance required for vent termina-
tion. Condensate could freeze and block vent pipe.