E 27
1. With burner removed (see F.1.m. above), check tubes
with ashlight for soot and remove with soft brush or
vacuum.
2. Spray tubes with high pressure water to remove any
foreign materials.
3. Check for corrosion
of burner, replace if
necessary
4. Reassemble
burner
and combustion assem-
bly as seen in gure 7.
E.1.n. Clean Gas Inlet
Screen (annu-
ally)
E.1.o. Examine Vent
System (annu-
ally)
1. Check all joints and
vent pipe connections
for tightness, corrosion
or deterioration.
2. At all connections
check for air leak while
unit is on low re so as not to burn yourself.
E.1.p. Examine Joint and Pipe Connections
(annually)
1. Check all water pipe connections for leaks while unit is
on low re.
2. If a leak is present around a tting attempt to tighten
the tting.
3. If a leak is present in the middle of the pipe, contact
factory.
E.1q. Corrosion Check (annually)
1. Check all gas, water, and air pipes to for corrosion and
deterioration.
2. If any corrosion or deterioration is present, please
contact factory.
Filter
Frame
Air
Filter
Air Box
Figure E.1. Air Filter Box Assembly
E.1.r. Combustion Test (annually)
Adjustments should be made to the gas valve until all read-
ings are within these recommended values.
Condition
Value
Acceptable Range
Carbon Monoxide:
ppm
Less Than 100 ppm
Carbon Dioxide:
%
Between 7- 9%
Excess Air:
%
30-45%
NOx:
ppm
Less Than 20 ppm
Comb. Chamber
Pressure:
WC
Under 0.5” WC