F 30
F. TROUBLESHOOTING
F.1. C
ONTROLLER LOCKOUT AND HOLD CODES
.
!
NOTE:
To support the recommended Troubleshooting, the Hon-
eywell SOLA controller has an Alert File. Review the Alert
history for possible trends that may have been occurring
prior to the actual Lockout.
Note Column: H= Hold message; L=Lockout message;
H or L= either Hold or Lockout depending on Parameter
Con guration
Code
Description
Recommended Troubleshooting of Lockout
Codes
Note
Safety Data Faults
1
Uncon gured safety data
1.
New Device, complete device con guration and safety
veri cation.
2.
If fault repeats, replace module.
L
2
Waiting for safety data veri cation
1.
Device in Con guration mode and safety parameters need
veri cation and a device needs reset to complete veri cation.
2.
Con guration ended without veri cation, re enter con gura-
tion, verify safety parameters and reset device to complete
veri cation.
3.
If fault repeats, replace module.
L
Internal Operation Errors
3
Internal fault: Hardware fault
Internal Fault.
1. Reset
Module.
2.
f fault repeats, replace module.
H
4
Internal fault: Safety Relay key feedback error
H
5
Internal fault: Unstable power (DCDC) output
H
6
Internal fault: Invalid processor clock
H
7
Internal fault: Safety relay drive error
H
8
nternal fault: Zero crossing not detected
H
9
Internal fault: Flame bias out of range
H
10
Internal fault: Invalid Burner control state
H
11
Internal fault: Invalid Burner control state ag
H
12
Internal fault: Safety relay drive cap short
H
13
Internal fault: PII shorted to ILK
H or L
14
Internal fault: HFS shorted to LCI
H or L
15
Internal fault: Safety relay test failed due to feedback ON
L
16
Internal fault: Safety relay test failed due to
safety relay OFF
L
17
Internal fault: Safety relay test failed due to
safety relay not OFF
L
18
Internal fault: Safety relay test failed due to
feedback not ON
L
19
Internal fault: Safety RAM write
Internal Fault.
1. Reset
Module.
2.
f fault repeats, replace module.
L
20
Internal fault: Flame ripple and over ow
H
21
Internal fault: Flame number of sample
mismatch
H
22
Internal fault: Flame bias out of range
H
23
Internal fault: Bias changed since heating cycle starts
H
24
Internal fault: Spark voltage stuck low or high
H
25
Internal fault: Spark voltage changed too much during ame
sensing time
H
Содержание Triton T-80