- 63 -
Operation with automatic control switch S8
“OFF”
Switch generator main switch S7 “ON”.
Generator is disconnected from socket.
Engine reaches nominal speed.
Generator is re-connected after 4 secs.
Power is now available until the generator main
switch S7 is turned “OFF”.
Operation with automatic control switch S8
“ON”
Switch generator main switch S7 “ON”.
Generator is disconnected from socket.
Engine reaches nominal speed.
Generator is re-connected after 4 secs.
If a consumer is connected, the engine goes on for
60 secs. before falling back to idle speed.
Generator is in standby. As soon as any consumer
is switched on, the routine is repeated from step 2.
Generator control box
Protective device
The generator is protected by circuit breakers that
switch off if a connected electrical device has an
electrical fault.
The insulation is monitored by relay K6.
When the yellow LED on the insulation monitoring
relay K6 is activated, it means that a serious insulation
fault has occured.
The insulation monitoring relay K6 is adjusted to
10 k
. This adjustment may not be changed.
The generator temperature is monitored by a thermal
contact (S6).
Generator 230/400V:
Q1
Main circuit breaker 4-pole + shunt trip coil
K6
Insulation monitoring relay
Generator 230V:
Q1
Main circuit breaker 3-pole + shunt trip coil
Q2
Circuit breaker 2-pole (for 12.5 kVA only)
K6
Insulation monitoring relay
Before connecting an electrical device,
always check the data listed on the rating
plate.
Avoid high inductive loads (e.g.
welding). High inductive loads can
damage the generator.