MAINTENANCE
Before carrying out any maintenance activity, check that the start switch is in position O and that no electrical power is
present on the terminals.
M
AINTENANCE SCHEDULE
Daily
Initial
Small
Normal
Yearly
50 hours
250 hours
500 hours
2000 hours
SERVICE PAK
–
With unit
2912 4112 05
2912 4113 06
2912 4114 07
For the most important subassemblies, Atlas Copco has developed service kits that combine all wear parts. These service kits offer you the
benefits of genuine parts, save on administration costs and are offered at reduced price, compared to the loose components. Refer to figure
1 of the parts list for more information on the contents of the service kits.
Coolant level
Check
Check
Check
Check
Check
Tension and condition of drive belt(s)
Check
Check
Check
Replace
Radiator and intercooler fins
Check/Clean
Check/Clean
Check/Clean
Check/Clean
Fuel pre-filter/Water separator
Check/Drain
Check/Drain
Check/Drain
Check/Drain
Check/Drain
Fuel filter element
Replace
Replace
Replace
Replace
Fuel injectors
Check
Oil level in sump
Check
Check
Check
Check
Check
Lubrication oil
Change
Change
Change
Change
Oil filter(s)
Replace
Replace
Replace
Replace
Air cleaner and dust bowl
Clean
Clean
Clean
Clean
Air filter element
(1)
Clean
Replace
Replace
Safety cartridge
Replace
Valve clearance
Check/adjust
Check/adjust
Check/adjust
Check/adjust
Oil, fuel and water leaks
Check
Check
Check
Check
Mechanical links (e.g. fuel solenoid link)
Grease
Grease
Grease
Level battery electrolyte
(2)
Check
Check
Check
Check
Condition of vibration dampers
Check
Check
Check
Check
Alternator insulation resistance
(*)
Measure
Measure
Measure
Measure
Tightness of nuts and bolts
Check
Check
Door hinges and locks
Grease
Grease
Fixation of hoses, cables and pipes
Check
Check
Inspection by Atlas Copco Service technician
11
I
NSTRUCTION MANUAL
(1) More frequently when operating in a dusty environment.
Evacuate dust from the airfilter valve daily.
(2) A Service Bulletin (ASB) dealing elaborately with batteries and
due care is available on request.
E
NGINE MAINTENANCE
Refer to the engine’s operator manual for full maintenance,
including instructions for changing the oil and cooling water
and replacing the fuel, oil and air filters.
(*) M
EASURING THE ALTERNATOR INSULATION RESISTANCE
A 500-V megger is required to measure the alternator
insulation resistance.
If the N-terminal is connected to the earthing system, it must
be disconnected from the earth terminal. Disconnect the
AVR.
Connect the megger between the earth terminal and terminal
L1 and generate a voltage of 500 V. The scale must indicate
a resistance of at least 5 M
Ω
.
Refer to the alternator operating and maintenance instruc-
tions for more details.
!
!