background image

10

QAS14 Yds

B

EFORE STARTING

– With the generator standing level, check the engine oil

level and top up if necessary. The oil level must be near to,
but not exceed the high mark on the engine oil level
dipstick.

– Check the coolant level in the expansion tank of the engine

cooling system. The water level must be near to the FULL
mark. Add coolant if necessary.

– Drain any water and sediment from the fuel pre-filter.

Check the fuel level and top up if necessary. It is recom-
mended to fill the tank after the day’s operation to prevent
waterdamp in a nearly empty tank from condensing.

– Check the vacuum indicator of the air filter. If the red part

shows completely, replace or clean the filter element.

– Press the vacuator valve of the air filter to remove dust. 

– Check the generator for leakage, tightness of wire termi-

nals, etc. Correct if necessary. 

– Check that the circuit breakers Q1, Q2 and Q3 are

switched off.

– Check that fuse F4 is not activated and that the emer-

gency stop is in the “OUT” position.

– Check that the load is switched off.

S

TARTING

– Insert the key in the starter switch and turn it to position I.

Wait until the preheat lamp goes out. Turn the key to
position     and release it as soon as the engine fires. The
switch automatically returns to position I.

Do not keep the key in its utmost position for more
than 10 seconds (maximum 20 seconds in extre-
mely cold conditions). Wait two minutes between
each starting attempt.

If the engine fails to start and for starting in extre-
mely cold conditions, consult your local Atlas Copco
dealer.

– Check that the warning lamps on the control and indicator

panel are out.

– Run the engine for approximately 5 minutes to warm up.

– Check the voltmeter P4 (with voltmeter selector switch S4

in different positions) and the frequency meter P5.

– Switch on circuit breaker Q1, together with trip coil. If

power supply is done by means of X2 or X3, respectively
switch on Q2 or Q3 as well.

– Switch on the load and check ammeter P3, voltmeter P4

(voltmeter selector switch in different positions) and
frequency meter P5.

D

URING OPERATION

Following points should be carried out regularly:

– Check the engine gauges and the lamps for normal

readings.

Avoid to let the engine run out of fuel. If it happe-
ned, priming will speed up the starting.

– Check for leakage of oil, fuel or cooling water.

– Avoid long low-load periods. In this case, an output drop

and higher oil consumption of the engine could occur.

– Check, by means of the generator gauges, that the voltage

between the phases is identical and that the rated current
in the third phase (L3) is not exceeded.

– When single-phase loads are connected to the generator

output terminals, keep all loads well-balanced.

If the circuit breakers are activated during operation, switch
off the load and stop the generator. Check and, if necessary,
decrease the load.

The generator’s side doors may only remain opened for short
periods during operation, to carry out checks for example.

S

TOPPING

– Switch off the load.

– Switch off the circuit breakers.

– Let the engine run for about 5 minutes.

– Stop the engine by turning the starter key to position O.

Withdraw the key.

– Lock the side doors and the door of the indicators and

control panel to avoid unauthorized access.

!

!

Содержание QAS14 YdS IT

Страница 1: ...sar Glosario Ordlista Glossario Ordliste Ordliste Gloss rio Sanasto 203 Instruction Manual and Parts List for AC Generators QAS14 Yds From following serial number onwards Geldig vanaf volgend serienum...

Страница 2: ...2 QAS14 Yds...

Страница 3: ...t prior notice CONTENTS Safety precautions for generators QAS 4 Leading particulars 5 General description 5 Bodywork 6 Markings 6 Drain plugs and filler caps 6 Control and indicator panel 6 Output ter...

Страница 4: ...breakers to OFF and stop the engine Correct the faulty condition before re starting 10 Never refill fuel while the machine is running Keep fuel away from hot pipes Never smoke while fuelling Do not s...

Страница 5: ...rthing rod 6 Side door access to control and indicator panel 7 Output terminal board 8 Hole for forklift A Alternator AF Air filter C Coupling DFO Drain flexible engine oil DFW Drain flexible cooling...

Страница 6: ...rd and the different earthing connections on the generator DRAIN PLUGS AND FILLER CAPS The drain holes for the engine oil the coolant and the plug for the fuel are located and labelled on the frame th...

Страница 7: ...l failure indicator Indicates that a shutdown appeared L3 Engine preheating system indicator Lights up when the glow plugs in the engine used to facilitate starting are warming up Extinguishes after a...

Страница 8: ...to IEC 364 3 i e one point in the power source directly earthed in this case the neutral The exposed conductive parts of the electric installation must be directly connected to the functional earth If...

Страница 9: ...s as listed in accordance with VDE 0298 installation method C3 Local regulations remain applicable if they are stricter than those proposed below Wire section mm2 2 5 4 6 10 16 25 35 50 70 95 Max curr...

Страница 10: ...sult your local Atlas Copco dealer Check that the warning lamps on the control and indicator panel are out Run the engine for approximately 5 minutes to warm up Check the voltmeter P4 with voltmeter s...

Страница 11: ...eplace Replace Safety cartridge Replace Valve clearance Check adjust Check adjust Check adjust Check adjust Oil fuel and water leaks Check Check Check Check Mechanical links e g fuel solenoid link Gre...

Страница 12: ...probe the outgoing current in the third phase L3 Compare the measured current with the current indicated on ammeter P3 Both readings should be the same 12 QAS14 Yds STORAGE OF THE GENERATOR STORAGE St...

Страница 13: ...ATOR TROUBLE SHOOTING Symptom Alternator does not excite After being excited alternator does not excite Low voltage at no load High voltage at no load Lower than rated voltage at load Higher than rate...

Страница 14: ...e tip clearances The engine runs erratically Fault in fuel control Restriction in a fuel pipe Fault in fuel lift pump Dirty fuel filter element Restriction in air filter cleaner or induction system Ai...

Страница 15: ...ure 18 C Engine Type YANMAR 3TNE88 ACG Rated net output 12 8 kW Load speed 1500 rpm Electrical system 12 V Battery 12 V 66 Ah Oil circuit capacity 7 l Cooling circuit capacity 3 1 l Fuel tank capacity...

Страница 16: ...16 QAS14 Yds...

Страница 17: ...1 2 2 7 6 6 4 4 7 11 11 5 5 1 1 1 1 2 2 12 2 12 a6 b3 c2 c3 c3 a3 P7 G W X10 X14 X14 S2 F4 X16 10A X16 X16 X16 X16 X16 X16 3 H1 X16 X18 X18 X18 X18 X18 X12 X10 X10 X10 X10 X10 X10 K2 K5 5 K5 K1 G1 E1...

Страница 18: ...ndicator Indicateur de niveau de carburant Me instrument f r Kraftstoffstand S2 Emergency stop button Noodstopknop Bouton arr t d urgence Not Aus Taste S7 Low fuel level switch Schakelaar laag brandst...

Страница 19: ...1 2 2 7 6 6 4 4 7 11 11 5 5 1 1 1 1 2 2 12 2 12 a6 b3 c2 c3 c3 a3 P7 G W X10 X14 X14 S2 F4 X16 10A X16 X16 X16 X16 X16 X16 3 H1 X16 X18 X18 X18 X18 X18 X12 X10 X10 X10 X10 X10 X10 K2 K5 5 K5 K1 G1 E1...

Страница 20: ...livello del combustibile Drivstoffm ler S2 Bot n de parada de emergencia Knapp f r n dstopp Pulsante di arresto di emergenza Knapp for sikkerhetsstopp S7 Interruptor bajo nivel de combustible Brytare...

Страница 21: ...1 2 2 7 6 6 4 4 7 11 11 5 5 1 1 1 1 2 2 12 2 12 a6 b3 c2 c3 c3 a3 P7 G W X10 X14 X14 S2 F4 X16 10A X16 X16 X16 X16 X16 X16 3 H1 X16 X18 X18 X18 X18 X18 X12 X10 X10 X10 X10 X10 X10 K2 K5 5 K5 K1 G1 E1...

Страница 22: ...ari S2 N dstopknap fi Bot o de paragem de emerg ncia H t pys ytyskytkin S7 Br ndstofniveaukontakt fi Comutador do n vel baixo de combust vel Alhaisen polttoainem r n merkkivalon kytkin S8 Kontakt h j...

Страница 23: ...N 32A d0 d0 c6 c54 X1 L3 N L2 L1 Q2 16A 30mA 20A Wire size a 1 mm 2 b 1 5 mm 2 c 2 5 mm 2 d 4 mm 2 e 6 mm 2 Colour code 1 brown 2 red 3 orange 4 yellow 5 green 6 blue 7 purple 8 grey 9 white 0 black L...

Страница 24: ...lemme ESPA OL SVENSKA ITALIANO NORSK F1 3 Fusible 4A S kring 4A Fusibile 4A Sikring 4 A G3 Generador Generator Generatore Generator P3 Amper metro 0 30A Amperem tare 0 30A Amperometro 0 30A Amperemete...

Страница 25: ...N 32A d0 d0 c6 c54 X1 L3 N L2 L1 Q2 16A 30mA 20A Wire size a 1 mm 2 b 1 5 mm 2 c 2 5 mm 2 d 4 mm 2 e 6 mm 2 Colour code 1 brown 2 red 3 orange 4 yellow 5 green 6 blue 7 purple 8 grey 9 white 0 black L...

Страница 26: ...ig fi 16 2 fi Disjuntor 16A 2 polar Virrankatkaisin 16 A 2 napainen R3 Udgangsmodstand Resist ncia limitadora Pudotusvastus S4 Voltmeterets omskifterknap fi Comutador selector do volt metro Volttimitt...

Страница 27: ...USE 6 3A BLACK BLACK RED GREEN RED RED BLACK GREEN RED 6 5 4 5 6 4 3 2 1 0 B 3 2 1 0 B P GREEN RED 180 CIRCUIT DIAGRAM DIAGRAMMA DEL CIRCUITO ELEKTRISCH SCHEMA KRETSSKJEMA SCHEMA DE CIRCUIT STR MDIAGR...

Отзывы: