- 104 -
10
Technical specifications for QAS 60 units
10.1 Readings on gauges
10.2 Settings of switches
10.3 Specifications of the engine/alternator/unit
Gauge
Reading
Unit
Ammeter L1-L3 (P1-P3)
Below max. rating
A
Voltmeter (P4)
Below max. rating
V
Switch
Function
Activates at
Engine oil pressure
Shut down
0.5 bar
Engine coolant temperature
Shut down
103°C
50 Hz
60 Hz
Reference conditions
1) 4)
Rated frequency
50 Hz
60 Hz
Rated speed
1500 rpm
1800 rpm
Generator service duty
PRP
PRP
Absolute air inlet pressure
100 bar(a)
100 bar(a)
Relative air humidity
30%
30%
Air inlet temperature
25°C
25°C
Limitations 2)
Maximum ambient temperature
50°C
50°C
Altitude capability
4000 m
4000 m
Maximum relative air humidity
85%
85%
Minimum starting temperature
-18°C
-18°C
Minimum starting temperature aided with coldstart equipment (optional)
-25°C
-25°C
Performance data 2) 3)
4) 5)
Rated active power (PRP) 3ph
48 kW
53.6 kW
Rated active power (PRP) 1ph
35 kW
39 kW
Rated power factor (lagging) 3ph
0.8 cos
0.8 cos
Rated power factor (lagging) 1ph
1 cos
1 cos
Содержание QAS 60 Pd
Страница 1: ...QAS 60 Pd S2A APP Instruction Manual for AC Generators English...
Страница 2: ......
Страница 88: ...88 6 4 2 3 Solving alarms Menu flow Qc4002 Qc4002 Qc4002 OR Qc4002 G OK LOG SOLVE PROBLEM See page 86...
Страница 111: ...111 Circuit diagrams...
Страница 115: ...115...
Страница 119: ...119...
Страница 128: ...128...
Страница 132: ...132...
Страница 139: ...139...
Страница 141: ......
Страница 142: ...Printed in Belgium 04 2012 2954 6280 00 www atlascopco com...