6000 Series
Wiring Diagrams
Electric Latch Retraction Exit Device
for Smoke Ventilation - Blow Open Function
(change factory pre-wiring to illustration below - move GND to COM)
• NOTE: This application must be approved by
local (AHJ) authority having jurisdiction.
• Door is normally closed and latched.
• Fire Alarm activation will retract exit device
latch bolt and door will automatically open.
Door will remain open until Fire Alarm
System has been reset.
• Door Operator’s main power input must be
wired into building’s back-up power supply.
• Exit device allows egress at all times,
including during power failures.
• Activation can be wall switch, card reader,
key switch, etc (Normally open momentary
dry contacts).
• If 3-position switch in Off position and Input
set to Blow Open, when signal is received from
Fire Alarm System, door WILL NOT open. If
3-position switch is On, door will open when
signal received from Fire Alarm System.
• If Input is set to Blow Open Override, door
WILL open when signal is received from Fire
Alarm System if 3-position switch is in On or
Off position.
• To turn on relay (Relay 2), Latch
Retraction (Output Connections,
page 14) and/or Open Delay (Set
options, page 8) features must
be turned on using adjustment
procedures on pages indicated.