Assa Abloy Norton 6000 Series Скачать руководство пользователя страница 1

80-9360-1043-020  Rev 1  05/21

6000 Series Full Feature Low Energy Operator 

Single Door Installation 

Programming Instructions

Onboard or Wi-Fi Smart Device

Copyright © 2021, ASSA ABLOY Accessories and Door Controls Group, Inc. All rights reserved. Reproduction in whole or 

in part without the express written permission of ASSA ABLOY Accessories and Door Controls Group, Inc. is prohibited.

These programming instructions guide setup of the 6000 operator installed 

on a single door via the onboard LCD screen or a Wi-Fi smart device.

Pour la version francaise voir www.nortondoorcontrols.com. 
READ AND FOLLOW ALL INSTRUCTIONS. SAVE THESE INSTRUCTIONS.

This product can expose you to lead which is known to the state of 

California to cause cancer and birth defects or other reproductive harm. 

For more information go to www.P65warnings.ca.gov.

WARNING

Содержание Norton 6000 Series

Страница 1: ...SSA ABLOY Accessories and Door Controls Group Inc is prohibited These programming instructions guide setup of the 6000 operator installed on a single door via the onboard LCD screen or a Wi Fi smart device Pour la version francaise voir www nortondoorcontrols com READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS This product can expose you to lead which is known to the state of California t...

Страница 2: ... Error Code Chart and Status Definitions 15 To Update 6000 Wi Fi Inverter 16 Wiring Diagrams Basic Single Door Using Factory Presets 17 Hard Wired Push Button 18 Wave to Open 19 RF Standard 20 Fail Secure Electric Strike 21 Fail Safe Electric Strike 22 Electric Dogging Exit Device 23 MKA2 x 24V 24 Electric Latch Retraction Powered Through 782N Controller 25 Electric Latch Retraction Smoke Ventilat...

Страница 3: ...ce by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help This device complies with Part 15 of the FCC Rules Operation is subject to the foll...

Страница 4: ...door open position output etc to green terminals on top of control board Figure 2 4 Reinstall Union Assembly using 4 8 32x5 16 screws previously removed 5 Turn on building power to unit 6 Confirm ON OFF HO switch is in ON position before proceeding to Setup Figure 3 NOTE On control board there should be one solid red LED for POWER and one white LED that flashes every 1 5 2 seconds for STATUS CLOSE...

Страница 5: ...REQUIRED GO Setup Using LCD Screen PULL 6011 PULL 110 Select operator model 1 After setting arm type push joystick UP to select operator model 2 Select specific operator model by pushing joystick LEFT or RIGHT Figure 6 Pull Figure 7 6011 PULL 110 deg 6051 PULL 110 deg PUSH Figure 8 or Figure 9 6021 PUSH 110 deg 6031 PUSH 110 deg 6061 PUSH 85 deg 6061 PUSH 90 deg 6061 PUSH 95 deg 6061 PUSH 100 deg ...

Страница 6: ...D should turn solid Let door close Figure 11 NOTE Any time door is in open position green LED should be solid NOTE If open position is not set within 30 seconds of setting closed position closed position must set again NOTE Once door has fully closed make sure there are no obstructions that could prevent door from opening Latching hardware must not prevent door from opening during following step 5...

Страница 7: ...e the lowest setting For example if the backcheck occurs at 75 degrees the full open shall be the time shown in Table I plus 1 5 seconds Doors of other weights and widths can be calculated using the formula T D ÖW 133 in US Units T D ÖW 2260 in SI metric Units Where T Time seconds D Door width inches mm W Door weight lbs kg The values for T time have been rounded up to the nearest half secound The...

Страница 8: ...other forces pushing on door OBST DET SENS Amount of time door will push against an obstruction before stalling or moving in opposite direction OPEN DELAY 1 Time before door will begin to open once activation has been received Set options Using joystick set options Figure 14 Continue with Input Connections on page 13 Figure 14 Max Open Force OPEN DELAY 2 Time before door will begin to open once ac...

Страница 9: ...E Operator will emit a long beep when Wi Fi has been successfully turned on Wi Fi automatically turns off after 20 minutes of inactivity For further security Wi Fi can be turned off immediately by selecting OFF on LCD screen or toggling 3 Position switch again Operator will emit a short beep when Wi Fi has been successfully turned off Operator serial number password and IP address are located insi...

Страница 10: ...r Setup Needed will be displayed if door setup has not been completed Setup To set up your operator select Setup page and proceed through four steps 1 Select Operator Model and Opening Range that matches your installation 2 Manually close door and select Set Closed Position 3 Open door to fully open position While holding door open select Set Open Position 4 Close door completely and select Learn ...

Страница 11: ...alue then save Speed Force and Timing Location settings must be adjusted to meet ANSI BHMA A159 19 American National Standard for Power Assist and Low Energy Power Operated Doors requirements for opening and closing based on door weight and width see tables page 7 Options Select setting and change value then save Save Restore Use this page to transfer settings setup from one operator to another 1 ...

Страница 12: ...ries Programming Instructions Wi Fi Method Connections Operator inputs and outputs can be customized from Connections page NOTE Input numbers are labeled on input PCB Outputs are labeled on main PCB To change function select input or output then scroll through drop down menu to select function NOTE For definitions see Input Connections on page 11 and Output Connections on page 12 Support Support p...

Страница 13: ...until the signal is discontinued Blow Open If 3 Position switch is in On position the door opens when signal is received from alarm system allowing air or smoke to flow through opening The door will stay open until signal from alarm system is stopped If the door is pulled away from open position operator will go back to open Blow Open Override With 3 Position switch in On or Off position the door ...

Страница 14: ...may be wired to external control systems or devices The function of each relay is selectable depending on the needs of the installation The outputs are labeled RLY 1 and RLY 2 like the wiring terminal blocks on the operator hardware Click Restore Defaults to set the input and output functions to factory default if needed Be sure to click Save after making changes These are the relay output functio...

Страница 15: ...programmed for various types of operation as the door opens and closes See the Connections page Relay 2 This is the state of relay number 2 on or off The relays maybe programmed for various types of operation as the door opens and closes See the Connections page 24V N O Output This is the state of the 24V normally open output on or off The normally closed output is always in the opposite state Err...

Страница 16: ...nd hold LOAD button for 3 seconds Release LOAD button when all LEDs light up 4 WARNING screens will appear Once Warnings have stopped scroll up to Update FIRMWARE screen Figure 22 5 Press joystick right to update 6 Confirm update by pressing joystick right Figure 23 7 Once updated Update SUCCESS will appear on screen Press joystick right to continue Figure 24 8 Remove USB from port 9 Once inverter...

Страница 17: ...ies and Door Controls Group Inc is prohibited 17 6000 Series Wiring Diagrams Basic Single Door Wiring Using Factory Presets Door is normally closed Activating either switch will open door Door will close after hold open time delay has expired Separate open delays are available for outside and inside activation delay Activation can be wall switch card reader key switch etc Normally open momentary d...

Страница 18: ...xpress written permission of ASSA ABLOY Accessories and Door Controls Group Inc is prohibited 18 6000 Series Wiring Diagrams Hard Wired Push Button Factory Pre Wiring Not Required to Change Door is normally closed Activating either switch will open door Door will remain in indefinite hold open until either switch is activated a second time causing door to close ...

Страница 19: ...rohibited 19 6000 Series Wiring Diagrams Wave to Open change factory pre wiring to illustration below move NO to 24 on controller Power N C C N O Power 1 Sec 5 Sec 10 Sec 15 Sec 20 Sec 25 Sec 30 Sec 35 Sec LED Setting Time Delay Setting Jumper in place LED is Red and flashes Green when relay is active No Jumper LED is Green and flashes Red when relay is active Wave to Open Switch Detail Wave to Op...

Страница 20: ...nd Door Controls Group Inc is prohibited 20 6000 Series Wiring Diagrams Radio Frequency Standard Function change factory pre wiring to illustration below move NO to 24 Door is normally closed Activating wireless switch or hand held wireless transmitter will open door Door will close after hold open time delay has expired Current draw at power outputs not to exceed 1 3A Alternate 24V Source V and V...

Страница 21: ...Electric Exit Device Door is normally closed and latched Activating switch will unlock electric strike or exit device and door will automatically open Door will close after hold open time delay has expired Door will remain locked during power failure Activation can be wall switch card reader key switch etc Normally open momentary dry contacts To turn on relay Relay 2 Latch Retraction Output Connec...

Страница 22: ...below move NO to NC on controller Door is normally closed and latched Activating switch will unlock electric strike or mag lock and door will automatically open Door will close after hold open time delay has expired Door will remain unlocked during power failure Activation can be wall switch card reader key switch etc Normally open momentary dry contacts Current draw at Power Outputs not to exceed...

Страница 23: ... depression on device touch bar will electrically dog device for push pull operation Door will now open automatically when wall switch is depressed Door will close after hold open time delay has expired Device will re latch during a power failure or when key switch is turned off Exit device allows egress at all times including during power failures Activation can be wall switch card reader key swi...

Страница 24: ... move NO to 24 Input 9 Security Override Continuous contact closure of this input triggers operator to disable input 2 Activation 2 This is typically used for switching off an outside wall plate MKA2 shown is in Normally Closed position which has LED RED and Exterior Wall Switch disabled To turn on relay Relay 2 Latch Retraction Output Connections page 14 and or Open Delay Set options page 8 featu...

Страница 25: ...ove GND to COM Door is normally closed and latched Activating switch will retract exit device latch bolt and door will automatically open Door will close after hold open time delay has elapsed Exit device allows egress at all times including during power failures Activation can be wall switch card reader key switch etc Normally open momentary dry contacts Contact Tech Support for other devices or ...

Страница 26: ...ill remain open until Fire Alarm System has been reset Door Operator s main power input must be wired into building s back up power supply Exit device allows egress at all times including during power failures Activation can be wall switch card reader key switch etc Normally open momentary dry contacts If 3 position switch in Off position and Input set to Blow Open when signal is received from Fir...

Страница 27: ...art without the express written permission of ASSA ABLOY Accessories and Door Controls Group Inc is prohibited 27 6000 Series Wiring Diagrams Hard Wired Executive Function Door is normally closed Activating either switch will open door Door will remain in indefinite hold open until either switch is activated a second time causing door to close ...

Страница 28: ...8 6000 Series Wiring Diagrams Radio Frequency Executive Function change factory pre wiring to illustration below move NO to 24 Door is normally closed Activating wireless switch or hand held wireless transmitter will open door Door will remain in indefinite hold open until wireless switch or hand held transmitter is activated a second time causing door to close Current draw at power outputs not to...

Страница 29: ...sh plate to activate transmitter 4 Attach transmitter to inside of electrical box and complete installation Removing Transmitter Code s Single Transmitter Code Press both Delay and No Delay Buttons simultaneously until Red LED flashes once approximately 1 second Press transmitter button twice within 10 seconds and transmitter code will be deleted All Transmitter Codes Press and hold both Delay and...

Страница 30: ...oor which will then open Activating inside door switch will open inside door After vestibule time delay has elapsed a signal will be sent to outside door which will then open Both doors will close when hold open time delay has elapsed Activating optional inside door switch located within corridor will open inside door only This door will re close after hold open delay has elapsed Activating option...

Страница 31: ...oor will close after hold open time delay has elapsed If door is closed and 585 Presence Detector senses something in the opening door will not open when activated If door is at open position and 585 Presence Detector senses something in the opening door will not close after hold open time delay has elapsed Once opening is clear door will close after hold open time delay has elapsed again NOTE For...

Страница 32: ...illustration below move NO to 24 596 Presence Sensor mounted to opening side or closing side of door on single opening Door is normally closed Activating switch will open door Door will close after hold open time delay has elapsed If using door mounted presence sensors For Closing Cycle sensor SS1 Input 4 to be set to Obstruction 1 For Opening Cycle sensor SS2 Input 3 to be set to Obstruction 2 Al...

Страница 33: ...n door reaches open position door drifts further open Decrease Hold Speed until door stops drifting Onboard see page 8 Wi Fi see page 11 When door reaches open position door bounces Decrease Slow Speed Onboard see page 8 Wi Fi see page 11 When signal is received operator tries to open door before auxiliary components are unlatched retracted 1 Confirm latch devices are getting proper power 2 Confir...

Страница 34: ... 2021 ASSA ABLOY Accessories and Door Controls Group Inc All rights reserved Reproduction in whole or in part without the express written permission of ASSA ABLOY Accessories and Door Controls Group Inc is prohibited Norton Technical Product Support Monroe NC 28112 USA Phone 800 438 1951 ext 6030 TechSupport Norton assaabloy com nortondoorcontrols com ...

Отзывы: