1BPROTECTION FUNCTIONS
PROTECTION, CONTROL AND METERING FUNCTIONS
Setting
Minimum
Maximum
Step
Notes
Time Multiplier
0,05
1,09
0,01
For IEC curves
0,5
30
0,01
For ANSI curves
0,5
15
0,01
For US curves
Time Adder
0
100
0,01
Definite time (s)
0
600
0,01
Table 2-22 Settings for each reclosing
2.1.15.6. FUNCTION DISABLE FOR EACH RECLOSURE (1, 2, 3
AND 4)
The function disable for each reclose is shown in Table 2-23
Function disabling
Notes
Instantaneous High and Low(50H, 50L)
YES/NO
Inverse Time (51)
YES/NO
Open phase(46OP)
YES/NO
Negative Sequence Definite Time(46DT)
YES/NO
Negative Sequence Inverse Time(46IT)
YES/NO
Table 2-23 Function disable
2.1.15.7. OTHER OPERATION FEATURES
Recloser out of service
This state is reached by disabling the recloser function (79). This function can
be performed by a control button or by a control command.
Definitive trip
This state is reached when, in addition to those already mentioned, one of the
following events occurs:
Breaker tripped Failure.
Breaker Close Failure.
Invalid voltage found by the Bus Side Voltage Supervision function at the
moment of the automatic close command.
Содержание smART P500
Страница 1: ...Instruction Manual Multifunction Protection Relay smART P500...
Страница 23: ...2BTABLES INDEX THIS PAGE HAS BEEN LEFT BLANK INTENTIONALLY...
Страница 39: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 9 Wye Wye Connection measured neutral...
Страница 40: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 10 Wye Wye Connection sensitive neutral...
Страница 41: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 11 Open Delta Connection measured neutral...
Страница 42: ...5BHARDWARE FEATURES INTRODUCTION Figure 1 12 Open Delta Connection sensitive neutral...
Страница 499: ...1BIEC 255 4 AND BS142 CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 1 Standard inverse IEC Curve...
Страница 501: ...1BIEC 255 4 AND BS142 CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 2 Very inverse IEC Curve...
Страница 503: ...1BIEC 255 4 AND BS142 CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 3 Extremely inverse IEC curve...
Страница 505: ...1BIEC 255 4 AND BS142 CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 4 Short inverse IEC curve...
Страница 507: ...1BIEC 255 4 AND BS142 CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 5 Long inverse IEC curve...
Страница 511: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 6 Moderately ANSI curve...
Страница 513: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 7 Very inverse ANSI curve...
Страница 515: ...2BANSI CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 8 Extremely inverse ANSI curve...
Страница 532: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 14 Recloser Curves 101 119...
Страница 535: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 15 Recloser Curves 120 142...
Страница 538: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 16 Recloser Curves 151 202...
Страница 541: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 17 Recloser Curves 25 Amp 35 Amp A B C D E...
Страница 544: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 18 Recloser Curves 50 Amp 70 Amp A B C D E...
Страница 547: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 19 Recloser Curves 100 Amp 140 Amp A B C D E...
Страница 550: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 20 Recloser Curves 160 Amp 185 Amp A B C D E...
Страница 553: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 21 Recloser Curves 225 Amp A B C D E...
Страница 556: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 22 Recloser Curves 280 Amp 280X Amp A B C D E...
Страница 559: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 23 Recloser Curves 400 Amp 400X Amp A B C D E...
Страница 562: ...4BRECLOSER CURVES 0BCURVES FOR TIME CHARACTERISTICS Figure I 24 Recloser Curves 560 Amp 560X Amp A B C D E...