40
Rev 2, 18.06.19
Variable
Description
Value
Condenser maximum temperature alarm. AMTC is not
blocked by BVC if there is an overlap.
0°C.....130°C
BVC<0°C = OFF
0°C.....130°C
>130°C OFF
BVC
Condenser max temp alarm must drop this many degree
points before alarm does not reappear onscreen.
Fan enablement during humidification. This function is
directly related to the humidifier.
Allows condenser fan to restart after this many degree
points.
0=DISABLED
1=ENABLED
1°C.....30°C
1°C.....30°C
VU
DMTC
AMTC
DVC
Condenser fan stop. If the BVC is higher than the
condenser probe reading, the fan stops. This function also
takes into consideration hot gas defrosting.
Default
1
10
°C
5
°C
48°C
10°C
FC
Duration of cooling cycle enablement. If the ambient
probe fails, it works for a total FC minutes. The FC
countdown starts at the end of the PFC time.
0 min.....120 min
0=DISABLED
15 min
Pause cooling cycle. This variable is only considered by
FC time.
Coolant level inlet status.
0 min.....120 min
0=DISABLED
0=NO
1=NC
PFC
LR
5 min
0
Door/s open alarm delay. A value below 0, disables the
alarm. A value of 0 creates an instant alarm. Once alarm is
triggered all functionality is stopped except alarm and
internal light.
0 min.....120 min
RAP
1 min
Freon high pressure inlet status.
0=NO
1=NC
PF
0
LUM
Humidification time limit. If humidification fails to reach
the humidity SET POINT within the LUM time, an alarm
will be triggered.
0 min.....120 min
0=DISABLED
0
VC
Enable hot ventilation only.
0=DISABLED
1=ENABLED
1
TF
Cold thermal inlet status.
0=NO
1=NC
0
Air change inlet status.
0=NO
1=NC
LO
0
Exclude PH probe.
0=DISABLED
1=ENABLED
ESPH
1