39
Rev 2, 18.06.19
Variable
Description
Value
Humidity management. If disabled, the humidity is not
shown on the display.
-20%.....0.....+20%
0=DISABLED
1=ENABLED
CSU
Exclude evaporator probe.
Ambient probe value correction.
Condenser probe value correction.
-20°C.....0.....+20°C
-20°C.....0.....+20°C
0=DISABLED
1=ENABLED
CSA
ESE
HR
CSC
Humidity probe value correction.
Default
To be
calibrated
To be
calibrated
To be
calibrated
1
1
ESC
Exclude condenser probe.
0=DISABLED
1=ENABLED
1
Defrost type, cycle inversion (with hot gas), resistance or
static. The cold output is also enabled with hot gas. Static
defrost will still reach the temperature the end of the
defrost cycle.
Minimum value that can be attributed to the temperature
set point.
1=HOT GAS
0=RESISTANCE
2=STATIC
-50°C.....+200°C
LST < HST by 1°C
SBR
LST
1
-3°C
Enable Heat.
0=DISABLED
1=ENABLED
CA
1
Maximum value that can be attributed to the temperature
set point.
-50°C.....+200°C
HST>LST by 1 °C
HST
35°C
DBF
Temperature differential with reference to the set point
for COLD BLOCK. This constitutes the SET -DBF limit
below which the cooling start relay and the
Dehumidification relay are disabled.
0°C.....+40°C
0°C
DBC
Temperature differential with reference to the set point
for HOT BLOCK. This constitutes the SET +DBF limit above
which the heating start relay and the Humidification relay
are disabled.
0°C.....+40°C
0°C
RATC
Alarm time delay for maximum condenser temperature.
0<= OFF
0=INSTANTANEOUS
0 min.....240 min
1 min
DEHUMIDIFICATION time limit. If dehumidification fails to
reach the humidity SET POINT within the LDE time, an
alarm will be triggered.
0 min.....240 min
0=DISABLED
LDE
0
SYSTEM VARIABLES continued