You can cross referance the follow variable codes with the list found on pages 36 - 41
Heating and cooling is managed in the neutral zone on the basis of the temperature set point
and the temperature differentials (parameters DTNC and DTNF). Cooling is activated when
the set point +(DTF value) is exceeded and remains enabled until the set point is reached
(with DTNF = 0). Heating is activated when the temperature goes below the set point -(DTNC
value) and remains enabled until the set point is reached (with DTNC = 0). It is possible to
set a “dead zone” with the parameters (DTNC) and (DTNF) which de-activates heating and
cooling when the temperature is between the set point -(DTNC) and the set point +(DTNF).
The parameter (TSF) creates a delay between the cooling system’s switch off and it’s
subsequent re-activation. Heating can be deactivated with the parameter CA (CA = 0
disables the heating relay under all conditions).
Neutral Zone
Cold On
Cold Off
Heat On
Heat Off
(SetºC)+DTF
(SetºC)+DTNF
(SetºC)+DTC
(SetºC)+DTNC
(SetºC)
Dehumidification
Activated
Humidification
Activated
ºC
Time(s)
Time(s)
Time(s)
1
0
1
0
TEMPERATURE MAINTENANCE
3.14