Tensor
7.2.2.5 Hysteresis run (motor start and stop)
Start and stop run of the engine can be influenced by a hysteresis function. e.g. to protect the mechanism and to increase the
reliability in operation.
H
.
b
Switch-off hysteresis
H
.
d
Switch-on hysteresis
With "Hb" (H-brake) the switch-off hysteresis of 0 - 80% is set. "Hd" (H-difference) defines a hysteresis between 0 - 90% for the
switch-on run. A value of 0% disables the hysteresis functions.
•
Select menu item „Hb“ or „Hd“ and open submenu with button [M].
•
Set a value between 0 and 8 or 9 for 80 % or 90 %. The difference of nominal value and actual value is then compared
with the hysteresis. If this difference is a) less than the switch-off hysteresis -> the drive stops, larger than the switch-on
hysteresis -> the drive regulates and moves.
7.2.2.6 Speed reduction
RPM speed reduction prior to switch-off point
t
.
P
•
Select menu item „rP“ and confirm with button [M].
•
In the submenu set the value between 0 (low speed reduction) and 9 (high speed reduction) for 90 %.
8.
Required customer information
8.1
Extraordinary situations
Run frequent testings during operation. Observe especially:
•
Intended use of the actuator (chapter 3.1);
•
unusual noise, heavy vibration or high temperatures;
•
check screws for tight seat;
•
check cable entries, cable glands and blank plugs for tight seat and possible leakness;
•
condition of electric wires.
If failure appear, set the actuator out of order and correct the error.
If you can not correct the error, contact an ARIS service person.
More information under: www.stellantriebe.de