Application Guide
P12y/EN AP/D32
MiCOM P125/P126 & P127
Page 25/74
2.4.4 Application
Considerations
The protection Pe> and Pe>> require relay current and voltage connections to be actived.
The measurement of the Pe depends on the voltage wiring of the relay.
In case of 3Vpn wiring the Ve will be equal to Ve= 1/3(Va+VB+VC) in the other insertions
way the applied voltage to the relay is directly used to calculate the Pe.
Referring to the relevant application diagram for the P125, P126 and P127 relays, it should
be installed such that its direction for forward operation is 'looking into' the protected feeder
i.e. away from the busbar, with the appropriate RCA .
Resistance earthed systems
180°
Insulated systems
270°
Petersen Coil system
200°
Transmission Systems (solidly earthed)
90°-120°
As illustrated in the relay application diagram, it is usual for the earth fault element to be
driven from a core balance current transformer. This eliminates the possibility of spill current
that may arise from slight mismatches between residually connected line CTs. It also
enables a much lower CT ratio to be applied, thereby allowing the required protection
sensitivity to be more easily achieved.
2.4.5
Iecos protection
The Iecos protection follows the same concepts of the Pe protection.
The difference is that the thresholds take in account the active component of the earth fault
current.
The setting of the RCA follows the above listed table.
2.4.6
Where use Iecos and where use Pe.
The wattmetric protection Pe/Iecos is almost used in the Petersen Coil systems.
In a Petersen Coil scheme during a fault we have a resistive current and an inductive
current.
The resistive current is constant because the residual voltage is always present; the
inductive current is the summation of the capacitive contribution of the healthy line and the
reactive contribution of the fault line.
In this situation is difficult to discriminate the line and detect the fault current value because
the capacitive and reactive are of opposite sign.
Since the residual voltage is present to the parallel between the coil and resistance a
wattmetric protection is used to be sure to open the fault line.
The unique resistive present component depends on the fault line.
The discriminative for the using of Pe or Iecos protection is the fault current value and the
relative fault operating boundary.
In some applications, the residual current on the healthy feeder can lie just inside the
operating boundary following a fault condition. The residual current for the faulted feeder lies
close to the operating boundary.
In this case, a correct discrimination is achieved by means of an Iecos characteristic, as the
faulted feeder will have a large active component of residual current, whilst the healthy
feeder will have a small value.
For insulated earth applications, it is common to use the Iesin characteristic that can be
obtained by the setting of the characteristic angle to 90° or 270°.
Содержание MiCOM P125
Страница 1: ...MiCOM P125 P126 P127 Directional Non directional Relay Technical Guide P12Y EN T E32...
Страница 2: ......
Страница 4: ...P12y EN T E32 Technical Guide Page 2 2 MiCOM P125 P126 P127 BLANK PAGE...
Страница 5: ...Pxxxx EN SS B11 SAFETY SECTION...
Страница 6: ......
Страница 8: ...Pxxxx EN SS B11 Page 2 10 Safety Section BLANK PAGE...
Страница 16: ...Pxxxx EN SS B11 Page 10 10 Safety Section BLANK PAGE...
Страница 17: ...Getting Started P12y EN GS D32 MiCOM P125 P126 P127 GETTING STARTED...
Страница 18: ......
Страница 66: ...P12y EN GS D32 Getting Started Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Страница 68: ......
Страница 70: ...P12y EN IN C22 Handling Installation and Case Dimensions Page 2 10 MiCOM P125 P126 P127 BLANK PAGE...
Страница 78: ...P12y EN IN C22 Handling Installation and Case Dimensions Page 10 10 MiCOM P125 P126 P127 BLANK PAGE...
Страница 79: ...User Guide P12y EN FT D32 MiCOM P125 P126 P127 USER GUIDE...
Страница 80: ......
Страница 166: ...P12y EN FT D32 User Guide Page 86 86 MiCOM P125 P126 P127 BLANK PAGE...
Страница 167: ...Technical Data P12y EN TD D32 MiCOM P125 P126 P127 TECHNICAL DATA AND CHARACTERISTIC CURVES...
Страница 168: ......
Страница 197: ...Application Guide P12y EN AP D32 MiCOM P125 P126 P127 APPLICATION GUIDE...
Страница 198: ......
Страница 202: ...P12y EN AP D32 Application Guide Page 4 74 MiCOM P125 P126 P127 BLANK PAGE...
Страница 273: ...Commissioning and Maintenance P12y EN CM C22 MiCOM P125 P126 P127 COMMISSIONING AND MAINTENANCE GUIDE...
Страница 274: ......
Страница 298: ...P12y EN CM C22 Commissioning and Maintenance Page 24 24 MiCOM P125 P126 P127 BLANK PAGE...
Страница 299: ...Connections and Wiring Diagrams P12y EN CO C22 MiCOM P125 P126 P127 CONNECTIONS AND WIRING DIAGRAMS...
Страница 300: ......
Страница 302: ...P12y EN CO C22 Connections and Wiring Diagrams Page 2 10 MiCOM P125 P126 P127 BLANK PAGE...
Страница 310: ...P12y EN CO C22 Connections and Wiring Diagrams Page 10 10 MiCOM P125 P126 P127 BLANK PAGE...
Страница 311: ...Commissioning Test and Record Sheet P12y EN RS D32 MiCOM P125 P126 P127 COMMISSIONING TEST AND RECORD SHEET...
Страница 312: ......
Страница 360: ...P12y EN RS D32 Commissioning Test and Record Sheet Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Страница 361: ......