Application Guide
P12y/EN AP/D32
MiCOM P125/P126 & P127
Page 19/74
2.4
Directional Earth Fault Protection (P125, P126 & P127)
The MiCOM P125, P126, P127 relays have a directional/non directional earth fault
protection.
It provides three directional/non directional earth overcurrent thresholds and two wattmetric
and active earth fault current thresholds.
The first and second threshold can be set as definite or inverse delay time using the IEC,
IEEE/ANSI, CO2-8, RI and RECT curves as shown in the Technical Data of the relays; for
the wattmetric protection ( Pe / IeCos ) only the first threshold can be set as definite or
inverse delay time, always using IEC, IEEE/ANSI, CO, RI and RECT curves.
The directional earth fault overcurrent protection element compares the earth fault current,
residual voltage with the set thresholds Ie>, Ue>, Ie>>, Ue>>, Ie>>>, Ue>>> and the relevant
angle between the Ie and Ue for each threshold. Once all the following listed requirements
are met the tripping command is set:
−
thresholds for Ie and Ue are exceeded (earth fault OC protection element)
−
Ie current vector is in the tripping area (Ie^Ue)
−
Ie [mA] + Ue [V] > 18 (Ien=1A) or Ie [mA] + Ue [V] > 90 (Ien=5A)
−
the tripping timer expires .
The protection's tripping area is defined by a tripping zone settable form ± 10° to ± 170° in
steps of 1° for each tripping threshold and a settable angle from 0° to 359° in steps of 1°
named torque/RCA angle (Ie^Ue), which can be separately set for each tripping threshold
and
The same threshold can be set as non-directional with definite or inverse delay time.
The third current threshold can be set as directional or non-directional but with only definite
delay time setting. The same applies to the Pe or IeCos second threshold.
The third threshold can work on the measured peak by an opportune choice in the dedicated
submenu. (See the FT part of the TG)
The peak detection is applied where a CT saturation condition occurs and the measure is not
more trustworthy.
The reset delay time for each threshold provides protection against intermittent faults.
Ue
Ie
RCA
Tripping zone is settable from:
±10˚ to ±170˚ in step of 1˚ with reference
to RCA (Torque angle)
RCA (Torque angle) is settable from
0˚ to 359˚ in step of 1˚
Forward
tripping zone
Backward
tripping zone
P0083ENa
The close figure shows the forward and
reverse tripping zone for the directional
earth fault protection.
The protection element also provides a non-sensitive area to avoid instability due to small
asymmetries and unbalances that can generally be present in the network system. This
condition is represented by the characteristic reproduced below, where the hatched area is
the tripping zone.
The tripping zone is limited by the equation Ie +(k x Ue) < (k x 18). (18 is a value derived
experimentally where stability is guaranteed).
Содержание MiCOM P125
Страница 1: ...MiCOM P125 P126 P127 Directional Non directional Relay Technical Guide P12Y EN T E32...
Страница 2: ......
Страница 4: ...P12y EN T E32 Technical Guide Page 2 2 MiCOM P125 P126 P127 BLANK PAGE...
Страница 5: ...Pxxxx EN SS B11 SAFETY SECTION...
Страница 6: ......
Страница 8: ...Pxxxx EN SS B11 Page 2 10 Safety Section BLANK PAGE...
Страница 16: ...Pxxxx EN SS B11 Page 10 10 Safety Section BLANK PAGE...
Страница 17: ...Getting Started P12y EN GS D32 MiCOM P125 P126 P127 GETTING STARTED...
Страница 18: ......
Страница 66: ...P12y EN GS D32 Getting Started Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Страница 68: ......
Страница 70: ...P12y EN IN C22 Handling Installation and Case Dimensions Page 2 10 MiCOM P125 P126 P127 BLANK PAGE...
Страница 78: ...P12y EN IN C22 Handling Installation and Case Dimensions Page 10 10 MiCOM P125 P126 P127 BLANK PAGE...
Страница 79: ...User Guide P12y EN FT D32 MiCOM P125 P126 P127 USER GUIDE...
Страница 80: ......
Страница 166: ...P12y EN FT D32 User Guide Page 86 86 MiCOM P125 P126 P127 BLANK PAGE...
Страница 167: ...Technical Data P12y EN TD D32 MiCOM P125 P126 P127 TECHNICAL DATA AND CHARACTERISTIC CURVES...
Страница 168: ......
Страница 197: ...Application Guide P12y EN AP D32 MiCOM P125 P126 P127 APPLICATION GUIDE...
Страница 198: ......
Страница 202: ...P12y EN AP D32 Application Guide Page 4 74 MiCOM P125 P126 P127 BLANK PAGE...
Страница 273: ...Commissioning and Maintenance P12y EN CM C22 MiCOM P125 P126 P127 COMMISSIONING AND MAINTENANCE GUIDE...
Страница 274: ......
Страница 298: ...P12y EN CM C22 Commissioning and Maintenance Page 24 24 MiCOM P125 P126 P127 BLANK PAGE...
Страница 299: ...Connections and Wiring Diagrams P12y EN CO C22 MiCOM P125 P126 P127 CONNECTIONS AND WIRING DIAGRAMS...
Страница 300: ......
Страница 302: ...P12y EN CO C22 Connections and Wiring Diagrams Page 2 10 MiCOM P125 P126 P127 BLANK PAGE...
Страница 310: ...P12y EN CO C22 Connections and Wiring Diagrams Page 10 10 MiCOM P125 P126 P127 BLANK PAGE...
Страница 311: ...Commissioning Test and Record Sheet P12y EN RS D32 MiCOM P125 P126 P127 COMMISSIONING TEST AND RECORD SHEET...
Страница 312: ......
Страница 360: ...P12y EN RS D32 Commissioning Test and Record Sheet Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Страница 361: ......