Application Guide
P12y/EN AP/D32
MiCOM P125/P126 & P127
Page 13/74
2.2.4 Setting
Guidelines
The applied current settings for directional overcurrent relays depend on the specific
application. In a parallel feeder arrangement, load current is always flowing in the non-
operating direction. Consequently the relay current setting may be less than the full load
rating of the circuit, typically 50% of In.
Note that the minimum setting that may be applied has to take into account the thermal
rating of the relay. Some electro-mechanical directional overcurrent relays have continuous
withstand ratings of only twice the applied current setting. Therefore 50% of rating was the
minimum setting that had to be applied.
With the latest generation relays the continuous current rating is 4 x rated current. If required
it is now possible to apply much more sensitive settings.
In a ring main arrangement, it is possible for load current to flow in either direction through
the point where the relay is located. Consequently the current setting must be above the
maximum load current, as in a standard non-directional application.
The required relay characteristic angle (RCA) settings for directional relays will depend on
the exact application in which they are used.
For instance for plain feeders where the zero sequence source is behind the relay, a RCA of
30° should be set.
The following picture shows the above examples.
RCA angle: 30˚
UA
UC
UB
IA
VBC
Normal
Fault
:
UA^IA=30˚
UA
UC
IA
VBC
P0359ENb
:
UA^IA=60˚- 80˚
90˚ connection, RCA 30˚ (lead)
Plain feeder, zero sequence source behind the relay
TRIP ZONE +/-90˚
IA fault
UB
On the P127 relay, it is possible to set the relay characteristic angle (RCA) or torque angle,
as it is also called, in the range of 0° to +359° in steps of 1°. The trip boundary zone
associated to the RCA is settable in the range from
±
10° to
±
170° in steps of 1°.
Further information about the setting range for the directional overcurrent protection are
available in the Technical Data document.
Содержание MiCOM P125
Страница 1: ...MiCOM P125 P126 P127 Directional Non directional Relay Technical Guide P12Y EN T E32...
Страница 2: ......
Страница 4: ...P12y EN T E32 Technical Guide Page 2 2 MiCOM P125 P126 P127 BLANK PAGE...
Страница 5: ...Pxxxx EN SS B11 SAFETY SECTION...
Страница 6: ......
Страница 8: ...Pxxxx EN SS B11 Page 2 10 Safety Section BLANK PAGE...
Страница 16: ...Pxxxx EN SS B11 Page 10 10 Safety Section BLANK PAGE...
Страница 17: ...Getting Started P12y EN GS D32 MiCOM P125 P126 P127 GETTING STARTED...
Страница 18: ......
Страница 66: ...P12y EN GS D32 Getting Started Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Страница 68: ......
Страница 70: ...P12y EN IN C22 Handling Installation and Case Dimensions Page 2 10 MiCOM P125 P126 P127 BLANK PAGE...
Страница 78: ...P12y EN IN C22 Handling Installation and Case Dimensions Page 10 10 MiCOM P125 P126 P127 BLANK PAGE...
Страница 79: ...User Guide P12y EN FT D32 MiCOM P125 P126 P127 USER GUIDE...
Страница 80: ......
Страница 166: ...P12y EN FT D32 User Guide Page 86 86 MiCOM P125 P126 P127 BLANK PAGE...
Страница 167: ...Technical Data P12y EN TD D32 MiCOM P125 P126 P127 TECHNICAL DATA AND CHARACTERISTIC CURVES...
Страница 168: ......
Страница 197: ...Application Guide P12y EN AP D32 MiCOM P125 P126 P127 APPLICATION GUIDE...
Страница 198: ......
Страница 202: ...P12y EN AP D32 Application Guide Page 4 74 MiCOM P125 P126 P127 BLANK PAGE...
Страница 273: ...Commissioning and Maintenance P12y EN CM C22 MiCOM P125 P126 P127 COMMISSIONING AND MAINTENANCE GUIDE...
Страница 274: ......
Страница 298: ...P12y EN CM C22 Commissioning and Maintenance Page 24 24 MiCOM P125 P126 P127 BLANK PAGE...
Страница 299: ...Connections and Wiring Diagrams P12y EN CO C22 MiCOM P125 P126 P127 CONNECTIONS AND WIRING DIAGRAMS...
Страница 300: ......
Страница 302: ...P12y EN CO C22 Connections and Wiring Diagrams Page 2 10 MiCOM P125 P126 P127 BLANK PAGE...
Страница 310: ...P12y EN CO C22 Connections and Wiring Diagrams Page 10 10 MiCOM P125 P126 P127 BLANK PAGE...
Страница 311: ...Commissioning Test and Record Sheet P12y EN RS D32 MiCOM P125 P126 P127 COMMISSIONING TEST AND RECORD SHEET...
Страница 312: ......
Страница 360: ...P12y EN RS D32 Commissioning Test and Record Sheet Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Страница 361: ......