Application Guide
P12y/EN AP/D32
MiCOM P125/P126 & P127
Page 29/74
2.7
Negative Sequence Overcurrent Protection (P126 & P127)
When applying traditional phase overcurrent protection, the overcurrent elements must be
set higher than maximum load current, thereby limiting the sensitivity of the element. Most
protection techniques also use an earth fault element operating from residual current, which
improves sensitivity for earth faults. However, certain faults may arise which can remain
undetected by such techniques.
Any unbalanced fault condition will produce negative sequence current of some magnitude.
Thus, a negative phase sequence overcurrent element can operate for both phase-to-phase
and phase to earth faults.
This section describes how negative phase sequence overcurrent protection may be applied
in conjunction with standard overcurrent and earth fault protection in order to alleviate some
less common application difficulties.
•
Negative phase sequence overcurrent elements give greater sensitivity to resistive
phase-to-phase faults, where phase overcurrent elements may not operate.
•
In certain applications, residual current may not be detected by an earth fault relay
due to the system configuration. For example, an earth fault relay applied on the delta
side of a delta-star transformer is unable to detect earth faults on the star side.
However, negative sequence current will be present on both sides of the transformer
for any fault condition, irrespective of the transformer configuration. Therefore, a
negative phase sequence overcurrent element may be employed to provide time-
delayed back-up protection for any un-cleared asymmetrical fault.
•
Where fuses protect motors on rotating machines, a blown fuse produces a large
amount of negative sequence current. This is a dangerous condition for the motor due
to the heating effects of negative phase sequence current at double frequency. A
negative phase sequence overcurrent element may be applied to provide efficient
back-up protection for dedicated motor protection relays.
•
It may also be required to simply set an alarm at the presence of negative phase
sequence currents on the system. Operators are then prompted to investigate the
cause of the unbalance.
The negative phase sequence overcurrent elements have a current pick up settings I2>,
I2>>, I2>>>, and are time delayed in operation by the adjustable timers tI2>, tI2>>, tI2>>>.
2.7.1
I2 Thresholds Setting Guidelines
This protection element includes three thresholds.
The first threshold can be set as DT or IDMT trip delay time.
The curves are the same as for the [50/51], [50N/51N] protection.
The current pick-up threshold (settable in the menu PROTECTION G1/[46] Neg. Seg. OC)
must be set higher than the normal negative phase sequence current due to the normal load
unbalance that is always present on the system. This can be set at the commissioning stage,
making use of the relay measurement function to display the standing negative phase
sequence current, and apply a setting at least 20% above.
Where the negative phase sequence element is required to operate for specific un-cleared
asymmetric faults, a precise threshold setting has to be based on an individual fault analysis
for that particular system due to the complexities involved. However, to ensure operation of
the protection element, the current pick-up setting must be set approximately 20% below the
lowest calculated negative phase sequence fault current for a specific remote fault condition.
The correct setting of the time delay is vital for this protection element. It should be also seen
that this element is applied primarily to provide back-up protection to other protective devices
or to provide an alarm. Therefore, it would be associated with a long delay time.
Содержание MiCOM P125
Страница 1: ...MiCOM P125 P126 P127 Directional Non directional Relay Technical Guide P12Y EN T E32...
Страница 2: ......
Страница 4: ...P12y EN T E32 Technical Guide Page 2 2 MiCOM P125 P126 P127 BLANK PAGE...
Страница 5: ...Pxxxx EN SS B11 SAFETY SECTION...
Страница 6: ......
Страница 8: ...Pxxxx EN SS B11 Page 2 10 Safety Section BLANK PAGE...
Страница 16: ...Pxxxx EN SS B11 Page 10 10 Safety Section BLANK PAGE...
Страница 17: ...Getting Started P12y EN GS D32 MiCOM P125 P126 P127 GETTING STARTED...
Страница 18: ......
Страница 66: ...P12y EN GS D32 Getting Started Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Страница 68: ......
Страница 70: ...P12y EN IN C22 Handling Installation and Case Dimensions Page 2 10 MiCOM P125 P126 P127 BLANK PAGE...
Страница 78: ...P12y EN IN C22 Handling Installation and Case Dimensions Page 10 10 MiCOM P125 P126 P127 BLANK PAGE...
Страница 79: ...User Guide P12y EN FT D32 MiCOM P125 P126 P127 USER GUIDE...
Страница 80: ......
Страница 166: ...P12y EN FT D32 User Guide Page 86 86 MiCOM P125 P126 P127 BLANK PAGE...
Страница 167: ...Technical Data P12y EN TD D32 MiCOM P125 P126 P127 TECHNICAL DATA AND CHARACTERISTIC CURVES...
Страница 168: ......
Страница 197: ...Application Guide P12y EN AP D32 MiCOM P125 P126 P127 APPLICATION GUIDE...
Страница 198: ......
Страница 202: ...P12y EN AP D32 Application Guide Page 4 74 MiCOM P125 P126 P127 BLANK PAGE...
Страница 273: ...Commissioning and Maintenance P12y EN CM C22 MiCOM P125 P126 P127 COMMISSIONING AND MAINTENANCE GUIDE...
Страница 274: ......
Страница 298: ...P12y EN CM C22 Commissioning and Maintenance Page 24 24 MiCOM P125 P126 P127 BLANK PAGE...
Страница 299: ...Connections and Wiring Diagrams P12y EN CO C22 MiCOM P125 P126 P127 CONNECTIONS AND WIRING DIAGRAMS...
Страница 300: ......
Страница 302: ...P12y EN CO C22 Connections and Wiring Diagrams Page 2 10 MiCOM P125 P126 P127 BLANK PAGE...
Страница 310: ...P12y EN CO C22 Connections and Wiring Diagrams Page 10 10 MiCOM P125 P126 P127 BLANK PAGE...
Страница 311: ...Commissioning Test and Record Sheet P12y EN RS D32 MiCOM P125 P126 P127 COMMISSIONING TEST AND RECORD SHEET...
Страница 312: ......
Страница 360: ...P12y EN RS D32 Commissioning Test and Record Sheet Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Страница 361: ......