9.4 Connecting the Outputs
79
Minute
Hour
Information content
provided by
third parties
Year
Month
R
A1
Z1
Z2
A2
S
1
2
4
8
10
20
40
P1
1
2
4
8
10
20
P2
1
2
4
8
10
20
1
2
4
Day of the
week
Calendar
Day
1
2
4
8
10
1
2
4
8
10
20
40
80
P2
P3
M
0
10
20
30
40
50
Figure 9.3: DCF77 Timing Diagram – see Marker Details
DCF77 Marker Details
M
minute marker (second marker No. 0): 0.1 s
R
second marker No. 15 indicates service request to the DCF77 signal generation system
A1
announcement of a forthcoming change from CET to CEST or vice versa
Z1, Z2
time zone indication: CET: Z1, 0.1 s, Z2 0.2 s; CEST: Z1 0.2 s, Z2 0.1 s
A2
announcement of a leap second, 0.2 s
P12, P2, P3
parity check bits
CET is Central European Time and CEST is Central European Summer Time. CET is UTC + 1:00, and
CEST is UTC + 2:00.
9.4
Connecting the Outputs
The clock comes equipped with Phoenix-style, screw terminal connectors, which are compatible with twisted
pair cabling.
To attach, strip the wires bare, DO NOT tin with solder, insert into the correct screw
terminal positions and tighten clockwise. Use a BNC breakout to adapt coaxial cabling to the clock terminal
connectors.
NOTE: If using a shielded, twisted-pair cable (like Belden 8760), connect the cable shield at only one
point and if possible at the clock. It has become best industry practice to ground time-code outputs from
clocks, and use galvanic isolation of time code inputs to IEDs.
1
William Dickerson, “Time in the Power Industry: How and Why We Use It,” www.arbiter.com, Resources,
Documentation
Содержание 1200B
Страница 4: ...iv ...
Страница 135: ...A 3 Physical Dimensions 117 Figure A 2 Suggested Mounting of the GNSS Surge Arrester ...
Страница 143: ...B 7 Four Fiber Optic Outputs 125 Figure B 4 Jumper Locations ...
Страница 145: ...B 8 8 Channel High Drive IRIG B Amplifier 127 Figure B 5 8 High Drive Outputs Jumper Locations ...
Страница 161: ...B 10 Four Additional Outputs and Dry Contacts 25 50 Vdc 143 Figure B 7 Option Connector Signal Locations ...
Страница 212: ...Appendix E Statement of Compliance The following page is a statement of compliance that includes Model 1201B and 1201C ...