20
pH B Configuration
This is used to control pH between two limits using Acid and Base. Push NEXT and pHB to
configure this. For more details refer to pH configuration.
Inhibitor Configuration
On the main screen, touch the Inhibitor parameter box. The Inhibitor screen will appear to allow
the user to set inhibitor settings. Setting values include MODE (including Disabled, Bleed,
Continuous, Flow, Water Meter, Corrosion and Flow (not available for all models)), PUMP SIZE,
DOSE RATE and OUTPUT. Press each parameter to input a value or chose pre-determined
options. (Picture 20)
Picture 20. Inhibitor screen
When Water Meter mode is selected, the system asks for PUMP SIZE and PPM (Part Per Million
of inhibitor). (Picture 21)
Picture 21. Inhibitor screen
OUTPUT box allows a different output for Inhibitor to be chosen. Please note
CAUTION
for ORP
and pH before setting OUTPUT.