Bio B Timer Example (Default)
The secondary biocide timer
Defaults
are explained as a proper example for accessory timers
Assume Bio B timer is set on Mondays at 08:00 for 1hr (Photo).
The following accessory timers can be set:
Accessory timer 1: Pre-Bleed for 15 minutes considering safety to avoid water waste
Output: Conductivity
Mode: Timer, Safety and Flow
Dur: mm: 15
Type: On Before