achieve the actual val-
ues
b.
The air in the supply tube ma-
nometer
Remove air from the tube
c.
Manometer is damaged
Replace manometer
9.
Deterioration of perme-
ate
Dirty or fouled RO membrane
Apply chemical cleaning of the
membrane, if it is not helpful , re-
place the membrane
10
Decreased flow rate
production of permeate
a. Clogged RO membrane
Apply chemical cleaning of the
membrane, if it is not helpful , re-
place the membrane
b.
The temperature of the
source water has changed
downwards
Calculate the flow rate production
in accordance with the real tem-
perature
*
modification of the system with automatic flushing module
9.
FLUSHING/CLEANING MODE IN PLACE (CIP)
Flushing/cleaning mode in place (CIP)
Your system is equipped with an option and corresponding entry for the chemical
flushing of the membranes. For flushing it is necessary to purchase a reagent
container (not included) for a capacity of 50 - 100 liters , with a flexible reinforced
piping , with a diameter larger than 1 ".the tank is filled by 1/2 - 2/3 of the flushing
solution. Also, you must have T-branches and locking valves on the line of the
permeate (product) and concentrate with outputs for flexible hoses (not included).
Flushing will be regulated by the pump.
To flush:
a.
Turn the valves on the line of the permeate to supply water to the flexible hose. The
hose should be lower in the reagent container.
b.
Fill the reagent container with osmosis water to the necessary capacity.
c.
Turn
the "CONTROL RO» to
"Off.".
d.
Switch valves of the line of the concentrate for feed on the flexible hose of
concentrate. Hose should be lower in the reagent container.
e.
Close the valve V-01 and RV-01, fully open the RV-03.
f.
Fully open the RV-02 in the models with the lack of drainage tap flushing.
g.
Connect the reagent container to the input denoted as «CIP», unscrewing the blind
(if it includes). Open the valve CIP (if it includes).
h.
Open the valve RV-01 by about 1/3.
i.
Turn
the "CONTROL RO» to
«CIP».
The pump will start to work and to intake the reagent from the tank. The reagent
which has passed through the system will drain back into the container by the hoses.
Continue the procedure for 3-5 minutes.