73
11.
SYSTEM INFORMATION COLLECTION VIA MODBUS
11.1 MODBUS COMMUNICATION PORT SETPOINTS
Modbus communication port are integrated in control panel. This provides communication from the control panel
to a field Modbus bus network. When powered, the water system will be able to communicate via the secondary
terminals labeled XT20-1A, XT20-1B, and XT20-G as a slave device.
Recommended Modbus cable has twisted-pair wires having an aluminum/mylar foil shield with drain wire.
11.2 VIEWING/SETTING MODBUS SETPOINTS
Modbus ID address can be viewed and set from the LCD display in setups mode - SETUP 17: "System ID Num-
ber" (1-255). Control panel are shipped with set default address of 001.
Modbus Settings: 9600 bits/second baud rate, even parity, and 1 stop bit.
11.3 NETWORK COMMUNICATION PROTOCOL
Only the Modbus RTU communication mode is recognized by the Control panel. The Control Panel can support
65 registers (130 data bytes) only in a single Modbus transaction. The Control panel responds to a limited number
of Modbus function codes. These are function codes 03 (Read Holding Registers) and 06 (Write Holding Regis-
ters).
Reading is carried out by one sending of all registers from address 0000 to address 0064. Writing is carried
in register with address 0000, which is used to write Control Word.
11.4 RO SETTINGS (READ ONLY)
Parameter
Address
Unit
Type
Device Type
0000
-
16-bit unsigned int
Config State * (Status word #1)
0001
-
32-bit unsigned int
Startup Flush
0003
sec.
16-bit unsigned int
Shutdown Flush
0004
sec.
16-bit unsigned int
Standby Flush
0005
h.
16-bit unsigned int
Valve Open Time (CL)
0006
sec.
16-bit unsigned int
Low Pressure Delay
0007
sec.
16-bit unsigned int
Full Tank Delay
0008
sec.
16-bit unsigned int
Dosing Pulse
0009
p/min
16-bit unsigned int
Flush Pulse min (HF)
0010
p/min
16-bit unsigned int
Flush Pulse Duration (HF)
0011
sec.
16-bit unsigned int
Periodic Flush h. (HF)
0012
f/h
16-bit unsigned int
Periodic Flush Duration (HF)
0013
sec.
16-bit unsigned int
Valve Flush Opening (CL)
0014
%
16-bit unsigned int
Valve Run Opening (CL)
0015
%
16-bit unsigned int
High Conductivity Alarm
0016
LPM
16-bit unsigned int
Feed High Conductivity Alarm
0017
LPM
16-bit unsigned int
Perm Flow K
0018
K
16-bit unsigned int
Feed Flow K
0019
K
16-bit unsigned int
Permeate Low Flow
0020
LPM (x10)
16-bit unsigned int
Concentrate Low Flow
0021
LPM (x10)
16-bit unsigned int
System Time
0022
unix time
32-bit unsigned int
System Status* (Status word #2)
0024
-
16-bit unsigned int
Содержание APRO 1000 LPH
Страница 1: ...aquaphor pro com TP APRO WH R02 APRO WH 1000 LPH WATER PURIFICATION SYSTEM...
Страница 8: ...8 aquaphor pro com TP APRO WH R03 2 SYSTEM OVERVIEW APRO WH 1000 LPH system dimensions...
Страница 9: ...9 aquaphor pro com TP APRO WH R03...
Страница 13: ...13 aquaphor pro com TP APRO WH R03 3 2 ELECTRIC CIRCUIT SCHEMES...
Страница 14: ...14 aquaphor pro com TP APRO WH R03...
Страница 15: ...15 aquaphor pro com TP APRO WH R03...
Страница 16: ...16 aquaphor pro com TP APRO WH R03...
Страница 17: ...17 aquaphor pro com TP APRO WH R03...
Страница 18: ...18 aquaphor pro com TP APRO WH R03...
Страница 19: ...19 aquaphor pro com TP APRO WH R03...
Страница 20: ...20 aquaphor pro com TP APRO WH R03...
Страница 80: ...80 14 ADDITIONAL MATERIALS...
Страница 81: ...81...
Страница 83: ...83 REMARKS...