PRELIMINARY INSTALLATION OPERATIONS
2.
Preparing electrical connections
2.1
Warning
!
The system must only be installed by skilled personnel quali
fi
ed in compliance with the regulations
of the country of installation (CEI 64 - 8 / EN 60335-1... standards)
The metallic components of the structure (i.e. the gate and pillars) must have an earth connection.
Aprimatic
9
6A
lc= 30mA
230 VAC
A rimatic
p
A rimatic
p
!
3
6
1
e
d
c
f
a
e
b
7
f
b
g
2
5
2
4
5
8
Preparation of the electrical layout
fi
g. 5 -
1
control unit
a
2 x 1.5 mm
2
+ earth
2
operator
b
3 x 1.5 mm
2
+ earth
3
antenna 433.92 MHz
c
supplied cable
4
fl ashing light
d
2 x 1 mm
2
5
photocell pair
e
transmitter 2 x 0.75 mm
2
; receiver 4 x 0.75 mm
2
6
7
key switch
OPTIONAL control devices
f
3 x 0.75 mm
2
(Proximity reader ; Magnetic card reader ; Electronic keypad)
8
electric lock (
OPTIONAL
)
g
2 x 1.5 mm
2
9
remote control
Prepare the electrical connection of the controller
•
and safety devices in accordance with the lay-out in
Fig.5
. Please heed the warnings provided in this
manual and comply with the instructions attached to the
installed components. Prepare the cableways (external
or buried) up to where the devices will be installed.
The electric component
•
box
is fully sealed and should
be placed at least 30 cm from the ground. Cable outlets
should point downwards. The cableway joints to the box
should be sealed to prevent the entry of dampness, insects
or small animals.
Always separate low voltage accessory cables from the
•
230V power supply.
POWER SUPPLY: 230V AC
•
- Cable 3x1.5mm
2
(minimum
section); the cable cross-section should be calculated in
accordance with the length of the line.
If it is necessary to use automation power supply cable
sheathing, apply this sheathing before connecting the cable
itself to the derivation boxes.
IMPORTANT!
•
Always install, upstream of the line, a mains
switch which guarantees a multipole cut-off with minimum
contact opening of 3 mm (connect it to a 6 A differential
overload switch - sensitivity of 30 mA).
The command and control accessory devices and the
•
emergency button should be placed within sight of the
automation, away from moving parts and at a minimum
height of 1.5 m from the ground.