Network Master Wiring
The Network Master is a hardware device used to
connect all display units at a location over a RS485
network, so feed inventory and water consumption
information can be collected and retrieved, either
locally or remotely via a call center server computer
that sends either text or email messages.
Feed-Link 3 is a windows based PC program that is
used to direct connect to the Network Master. This
information can be accessed real time from either
a PC directly connected to the Network Master or
remotely through an internet connection.
The Network Master comes with jacks for ethernet
and PC connections. It has plugs for power and
RS485 communication.
Network Master Technical Specifications:
Supply: 24 VDC, 50/60 Hz, overload and over
voltage protection fuses F1, F2-1/4A slow blow.
Enclosure: NEMA 4X
Maximum number of bins: 50
Maximum network distance: 4000'
Network wire: Two (2) conductor 18 AWG
shielded cable.
Operating systems: Win95 and later.
Figure 7F Inside of the Network Master
Connecting the 24 VDC Power to Network Master
The Network Master comes with a 115 VAC to 24 VDC transformer. Connect wires from the transformer
to 24 VDC power terminals on back of the Network Master. Connect black wire from the transformer to the
terminal marked “24 VDC -” on the Network Master. Connect the red wire from the transformer to the
terminal marked “24 VDC +” on Network Master. Connect green wire from the transformer to the terminal
marked “Earth” on Network Master.