Spare Parts
GT3000
80
IMGT30017EN
Always with the drive disconnected from the power source, set the board just installed.
Set the jumpers and the dipswitch of the new board at the same way of the replaced board.
See the jumpers and the dipswitch function table at chapter 3.
NOTE:
The the SCADA PLUS board has the jumper JP 2 with three positions and it must be set according the GT3000 size.
The SVGT420 has a dedicated SCADA BASIC board (code 1000001377)
SVGT0P3-166 F/Y
SVGT640-670 F
SVGT105-960 K/J
JUMPER
Position
Board
Position
Board
Position
Board
JP2
Open
Basic / Plus
1-2
Plus
Open
Plus
JP3
2-3
Basic / Plus
1-2
Plus
1-2
Plus
SVGT200-340 F
SVGT420-470F
SVGT780F-940M
JUMPER
Position Board Position Board Position Board
JP2 1-2 Plus 2-3 Plus 2-3 Plus
JP2 Closed Basic Closed Basic
JP3
1-2
Basic / Plus
1-2
Basic / Plus
1-2
Plus
The first compulsory thing to do is to set the proper drive size.
GT3000 (SW) size setting
GT3000 size
The size of the spare boards is set to “indefinite”: so after the board replacing it is necessary to set the proper GT3000 size.
With the inverter powered and terminal board XM1 disconnected, by the keypad or by the PC interface set the parameter
Drive Size Select
[06.01]
In Drive Menu ([06.00] Drive Data Family).
Read the GT3000 size on the nameplate attached to the drive e.g. SVGT125 value to set 125.
The values are set from a firmware list.
NOTE
The parameter [06.01] is available at level 4 only; the spare board is at level 4 as default but the reset the level 4 is no
more available.
The level 4 password is reserved. Contact the ”Service” for any need.
Initialization Reset
After the set of the parameters above-mentioned it is necessary to reset the drive in order to set the default value of the size:
Set the parameter [01.03] Reset All = ON in Motor Menu Family [01.00] Main Setting
Confirm and wait until the internal calculation is finished.
At the end of the initialisation phase the control is at programming level 1(Quick Start).
At this moment, if it is available the back up file of the user parameters, you can do the parameter download or, in the contrary, you can set
the parameters according to plant requirements.
CAUTION
Содержание GT3000
Страница 1: ...GT3000 Hardware Software Manual www answerdrives com ...
Страница 2: ......
Страница 4: ......
Страница 8: ...Table Of Contents GT3000 iv IMGT30017EN ...
Страница 12: ...General Safety Precautions viii IMGT30017EN ...
Страница 25: ...GT3000 Technical Data IMGT30017EN 13 Frames IV V VIN SVGT045 166 IP20 ...
Страница 26: ...Technical Data GT3000 14 IMGT30017EN Frames IV V VIN SVGT045 166 IP54 ...
Страница 27: ...GT3000 Technical Data IMGT30017EN 15 Frames IV V IP20 NEMA1 SVGT105 170K J Peso 65Kg Weight 143Lbs ...
Страница 28: ...Technical Data GT3000 16 IMGT30017EN Frames VII VIII IP00 SVGT200 521K SVGT200 470F ...
Страница 29: ...GT3000 Technical Data IMGT30017EN 17 F series Frames 2xVII 2xVIII Parallel IP00 SVGT520 940M ...
Страница 30: ...Technical Data GT3000 18 IMGT30017EN K series Frames 2xVII 2xVIII Parallel IP00 SVGT580 960K ...
Страница 32: ...20 IMGT30017EN 3A 1 3 Lifting Frame VII VIII Figure 2A 1 Methods of Unloading and Lifting GT3000 Drives ...
Страница 36: ...Installation GT3000 24 IMGT30017EN 3A 2 1 4 Frames VII VIII Installatiion ...
Страница 58: ...GT3000 Installation 46 IMGT30004EN ...
Страница 107: ...GT3000 Terminal Boards and Power Schematics IMGT30017EN 95 ...
Страница 108: ...Terminal Boards and Power Schematics GT3000 96 IMGT30017EN SVGT200 260 320K J Motor earth connection Field bus ...
Страница 109: ...GT3000 Terminal Boards and Power Schematics IMGT30017EN 97 SVGT390 521K J Field bus Motor earth connection ...
Страница 110: ...Terminal Boards and Power Schematics GT3000 98 IMGT30017EN ...