GT300
Installation
IMGT30017EN
31
3A.4
Reactors
3A.4.1
Input line reactors
An AC line reactor can be used, provided it meets IEEE 587 standards for transient protection. The reactor causes a voltage drop proportional to
the supply current and to the inductance value; select a reactor to have a voltage drop equal to 2 – 5 % of the rated input voltage (when the drive is
conducting full rated current).
Line Reactor Function:
• Reduces RMS ripple currents in bus capacitors
• Protects against unbalanced and signal phase condition
• Protects the drive from line side transients
• Improves the true power factor
• Reduces nuisance tripping from input voltage spikes
• Reduces input current harmonics
• Provides RFI suppression
Input Line reactors absorb power line disturbances that could otherwise damage or shutdown the drive or other sensitive equipment.
Line Reactors reduce generated harmonics helping to meet the IEEE-519, 1993 guidelines for harmonic limitation.
The GT3000 frame IIIN, IVN, VN, VIN 6p AC power supply have a 2,5% internal reactor, other frames needs input reactor between mains and drive if:
A
a thyristor converter or other drives are operating on the same line.
B
power factor correction capacitors are connected to the same line.
C
the supply voltage unbalance exceeds 3%.
Example: Vrs = 400V, Vst = 407V, Vtr = 390V.
V
V
V
V
3
399V
M
rs
st
tr
2,3%
399
9
100
V
V
from
deviation
max.
100
F
M
M
s
D
The supply line power and the drive power are included in the highlighted area:
3A.4.2
Output reactors
Waveform generation from a typical pulse width modulated (PWM) motor drive has the potential to excite motor cable resonance-producing
voltages in excess of 3 to 3 times the DC bus voltage at the motor terminals. The GT3000 product line was designed to compensate the capacitive
dispersion current to ground and to reduce the voltage gradient on the motor. Reactors, together with the ferrite cores, help RFI phenomena
attenuation.
CAUTION:
In case of motors in parallel, it is necessary to take into account the sum of the lengths of all motor cables
Limit the length of the motor cables so as not to exceed a voltage drop of 3 ÷ 5 % at the rated current.
NOTE:
The input reactor and output reactors codes are in table 3A.5
500
2500
Supply line power
50
250
Drive size
Not required
Line reactor required
[kVA]
[kVA]
Vrs, Vst, Vtr : rms value of line-to-line voltages
Vm : mean value of Vrs, Vst, Vtr
Fs : voltage unbalance
In this example a reactor is not necessary
Содержание GT3000
Страница 1: ...GT3000 Hardware Software Manual www answerdrives com ...
Страница 2: ......
Страница 4: ......
Страница 8: ...Table Of Contents GT3000 iv IMGT30017EN ...
Страница 12: ...General Safety Precautions viii IMGT30017EN ...
Страница 25: ...GT3000 Technical Data IMGT30017EN 13 Frames IV V VIN SVGT045 166 IP20 ...
Страница 26: ...Technical Data GT3000 14 IMGT30017EN Frames IV V VIN SVGT045 166 IP54 ...
Страница 27: ...GT3000 Technical Data IMGT30017EN 15 Frames IV V IP20 NEMA1 SVGT105 170K J Peso 65Kg Weight 143Lbs ...
Страница 28: ...Technical Data GT3000 16 IMGT30017EN Frames VII VIII IP00 SVGT200 521K SVGT200 470F ...
Страница 29: ...GT3000 Technical Data IMGT30017EN 17 F series Frames 2xVII 2xVIII Parallel IP00 SVGT520 940M ...
Страница 30: ...Technical Data GT3000 18 IMGT30017EN K series Frames 2xVII 2xVIII Parallel IP00 SVGT580 960K ...
Страница 32: ...20 IMGT30017EN 3A 1 3 Lifting Frame VII VIII Figure 2A 1 Methods of Unloading and Lifting GT3000 Drives ...
Страница 36: ...Installation GT3000 24 IMGT30017EN 3A 2 1 4 Frames VII VIII Installatiion ...
Страница 58: ...GT3000 Installation 46 IMGT30004EN ...
Страница 107: ...GT3000 Terminal Boards and Power Schematics IMGT30017EN 95 ...
Страница 108: ...Terminal Boards and Power Schematics GT3000 96 IMGT30017EN SVGT200 260 320K J Motor earth connection Field bus ...
Страница 109: ...GT3000 Terminal Boards and Power Schematics IMGT30017EN 97 SVGT390 521K J Field bus Motor earth connection ...
Страница 110: ...Terminal Boards and Power Schematics GT3000 98 IMGT30017EN ...