Installation
GT3000
IMGT30017EN
109
Connections of the cables of the drive and motor
Connections Inverter - Motor with symmetrical shielded cable
a
Highlight the connection between the frame of the motor and the ground
bar of the GT3000 panel performed by means of drive-motor connection
cables (shield and PE conductors).
Drive – Motor connections with two shielded cables
Connections – converter side:
a) The PE conductors and the shields must be connected to the ground bars of the converter panel.
b) If due to the current load it is necessary to use more parallel-connected cables, the three conductors of each three-phase cable must be connected
to the phases U, V, and W.
Connections – motor side:
a) The PE conductors and the shields must be connected to the frame of the motor; therefore, on the terminal board of the motor it must be foreseen a
proper fastening plate.
b) Should it be necessary to use more parallel-connected cables, the three conductors of each three-phase cable must be connected to the phases U,
V, and W.
NOTE: Long shielded motor cables may cause external ground fault detector trips, due to leakage currents to ground and high switching frequency.
Replace the external ground fault detector with a less sensitive one or feed the drive with an isolation transformer.
Ferrite
In the applications in which various motors are connected to one inverter and it is not possible to carry
out the complete shielding of the cables because of a shunt terminal board of the single motor (shielded)
cables, it is necessary to provide toroids in the inverter output. In order to use them correctly it is
necessary to wind the three cables (from 2 up to 5 times) within the core leaving the earth cable outside.
The part of cable from the inverter to the shunt terminal board, without braiding, shall be as short as
possible.
The SVGT0P3-166F provides an internal mono-loop ferrite ring out coming to motor.
SVGT0P3-028 feed in DC bus
In applications in which SVGT0P3-028, fed in DC bus, are used it is necessary to provide
ferrite in the drive input. For correct use, wind the two cables 2 to 3 times through the
ferrite keeping the ground cable outside.
Ferrite SAP code: ELC201767
Figure A2.5 Use of Ferrite
Grounding
The inverter panel and the motor are connected singularly to the same grounding system. The connection cables between Inverter and Motor are
grounded on both sides (both the PE conductors and the shields of these cables).
Содержание GT3000
Страница 1: ...GT3000 Hardware Software Manual www answerdrives com ...
Страница 2: ......
Страница 4: ......
Страница 8: ...Table Of Contents GT3000 iv IMGT30017EN ...
Страница 12: ...General Safety Precautions viii IMGT30017EN ...
Страница 25: ...GT3000 Technical Data IMGT30017EN 13 Frames IV V VIN SVGT045 166 IP20 ...
Страница 26: ...Technical Data GT3000 14 IMGT30017EN Frames IV V VIN SVGT045 166 IP54 ...
Страница 27: ...GT3000 Technical Data IMGT30017EN 15 Frames IV V IP20 NEMA1 SVGT105 170K J Peso 65Kg Weight 143Lbs ...
Страница 28: ...Technical Data GT3000 16 IMGT30017EN Frames VII VIII IP00 SVGT200 521K SVGT200 470F ...
Страница 29: ...GT3000 Technical Data IMGT30017EN 17 F series Frames 2xVII 2xVIII Parallel IP00 SVGT520 940M ...
Страница 30: ...Technical Data GT3000 18 IMGT30017EN K series Frames 2xVII 2xVIII Parallel IP00 SVGT580 960K ...
Страница 32: ...20 IMGT30017EN 3A 1 3 Lifting Frame VII VIII Figure 2A 1 Methods of Unloading and Lifting GT3000 Drives ...
Страница 36: ...Installation GT3000 24 IMGT30017EN 3A 2 1 4 Frames VII VIII Installatiion ...
Страница 58: ...GT3000 Installation 46 IMGT30004EN ...
Страница 107: ...GT3000 Terminal Boards and Power Schematics IMGT30017EN 95 ...
Страница 108: ...Terminal Boards and Power Schematics GT3000 96 IMGT30017EN SVGT200 260 320K J Motor earth connection Field bus ...
Страница 109: ...GT3000 Terminal Boards and Power Schematics IMGT30017EN 97 SVGT390 521K J Field bus Motor earth connection ...
Страница 110: ...Terminal Boards and Power Schematics GT3000 98 IMGT30017EN ...