GT3000
Technical
Data
IMGT30017EN
9
2A.7 Cooling
GT3000 (except for SVGT0P3 to 0P6) provides an internal fan. Air intake is from bottom. Refer to the following table when sizing enclosures:
Table 2A.7 Cooling Specifications
Output Current
Power Losses
Ventilation
Cooling Fan Rated Data
Cl.1
Cl.2
Cl.1 Cl.2
Control Capacity
Voltage
Current
Drive
A
A
W W W m
3
/h
ft
3
/s V
A
SVGT0P3F
3.8
2.1
45 22 30 NA NA Not
available
NA
SVGT0P4F
5.6
3.8
66 45 30 NA NA Not
available
NA
SVGT0P6F
9.5
5.6
120 66 30 NA NA
Not
available
NA
SVGT008F
12
9.5
165 120 30 66 36
Not
available
NA
SVGT011F
16
12
225 165 30 100 59
Not
available
NA
SVGT015F
21
16
276 225 30 100
59 Not
available NA
SVGT018F
25
21
330 276 30 100
59 Not
available NA
SVGT022F
32
25
450 330 30 100
59 Not
available NA
SVGT028F
40
32
555 450 40 100
59 Not
available NA
SVGT030F/Y
40
32
555
450
40
100
59
Not available
NA
SVGT036F/Y
52
40
660
555
40
100
59
Not available
NA
SVGT045F/Y
65
52
900
660
50
280
164
Not available
NA
SVGT053F/Y
77
65
1100
900
50
280
164
Not available
NA
SVGT066F/Y
96
77
1350
1100
50
280
164
Not available
NA
SVGT086F/Y
124
96
1650
1350
60
280
164
Not available
NA
SVGT108F/Y
156
124
2250
1650
60
280
164
Not available
NA
SVGT125F/Y
180
156
2700
2250
60
500
293
230V 50/60Hz
0,9
SVGT150F/Y
210
180
3300
2700
80
500
293
230V 50/60Hz
0,9
SVGT166F/Y
240
200
3300
2700
80
500
293
230V 50/60Hz
0,9
SVGT200F/Y
302
240
3960 3300 80 800 471 230V
50/60Hz
1.45
SVGT250F/Y
361
302
4800 3960 100 800 471
230V
50/60Hz
1.45
SVGT292F/Y
420
370
6900
6000
100
1400
824
400V/50Hz - 440V/60Hz
3.4 / 4.4
SVGT340F/Y
510
420
7500 6500 100 1400
824
400V/50Hz - 440V/60Hz
3.4 / 4.4
SVGT420F/Y
610
480
9000 7800 100 1400
824
400V/50Hz - 440V/60Hz
3.4 / 4.4
SVGT470F/Y
680
520 10000 7800 100 1400
824
400V/50Hz - 440V/60Hz
3.4 / 4.4
SVGT520F/Y
800
620
10800
8000
200
2x1400
2x824
400V/50Hz - 440V/60Hz (3.4 / 4.4) X 2
SVGT580F/Y
840
740
12150 8500 200 2x1400
2x824
400V/50Hz - 440V/60Hz (3.4 / 4.4) X 2
SVGT670F/Y
1020
840
14000 11000 200 2x1400
2x824
400V/50Hz - 440V/60Hz (3.4 / 4.4) X 2
SVGT780F/Y
1220
960
16400 12500 200 2x1400
2x824
400V/50Hz - 440V/60Hz (3.4 / 4.4) X 2
Three-phas
e s
uppl
y v
ol
tage 400V
, 415V
, 440V
, 460V
, 480
V
±
10%
SVGT940M/Y
1360
1040 20000 15600 200 2x1400
2x824
400V/50Hz - 440V/60Hz (3.4 / 4.4) X 2
SVGT105K/J
90
76
1500 1350 80 400 235
230V
50/60Hz
0.9
SVGT130K/J
110
90
1800 1500 80 400 235
230V
50/60Hz
0.9
SVGT170K/J
145
110
3400 1800 80 400 235
230V
50/60Hz
0.9
SVGT200K/J
170
135
3900 3400 100 800 471 230V
50/60Hz
1.45
SVGT260K/J
220
180
3600 3000 100 800 471
230V
50/60Hz
1.45
SVGT320K/J
270
210
4400 3500 100 800 471
230V
50/60Hz
1.45
SVGT390K/J
330
260
5400 4300 100 1400 824 400V/50Hz
-
440V/60Hz 3.4/4.4
SVGT1480K/J
400
320
6500 5200 100 1400 824 400V/50Hz
-
440V/60Hz 3.4/4.4
SVGT521K/J
440
350
7200 5300 100 1400 824 400V/50Hz
-
440V/60Hz 3.4/4.4
SVGT640K/J
540
420
8800
7000
200
2x1400
2x824
230V 50/60Hz
(1.45) x 2
SVGT780K/J
660
520
10800
8600
200
2x1400
2x824
400V/50Hz - 440V/60Hz (3.4 / 4.4) x 2
Three-phas
e s
uppl
y v
ol
tage 535V
, 575V
,
600V
, 660V
, 690V
±
15
%
SVGT1960K/J
800
620
13000
10400
200
2x1400
2x824
400V/50Hz - 440V/60Hz (3.4 / 4.4) x 2
%
The GT3000 fans are made to provide for losses of the drives only. During the installation in an
enclosure, it is necessary to take into account auxiliary component losses.
%
SVGT125-166F/Yand SVGT105-960K/J The user must provide a protection device for the fan.
%
SVGT200F-940M/Y Inside the drive there is a Magneto-thermal switch for the fan protection.
WARNING
☞
Содержание GT3000
Страница 1: ...GT3000 Hardware Software Manual www answerdrives com ...
Страница 2: ......
Страница 4: ......
Страница 8: ...Table Of Contents GT3000 iv IMGT30017EN ...
Страница 12: ...General Safety Precautions viii IMGT30017EN ...
Страница 25: ...GT3000 Technical Data IMGT30017EN 13 Frames IV V VIN SVGT045 166 IP20 ...
Страница 26: ...Technical Data GT3000 14 IMGT30017EN Frames IV V VIN SVGT045 166 IP54 ...
Страница 27: ...GT3000 Technical Data IMGT30017EN 15 Frames IV V IP20 NEMA1 SVGT105 170K J Peso 65Kg Weight 143Lbs ...
Страница 28: ...Technical Data GT3000 16 IMGT30017EN Frames VII VIII IP00 SVGT200 521K SVGT200 470F ...
Страница 29: ...GT3000 Technical Data IMGT30017EN 17 F series Frames 2xVII 2xVIII Parallel IP00 SVGT520 940M ...
Страница 30: ...Technical Data GT3000 18 IMGT30017EN K series Frames 2xVII 2xVIII Parallel IP00 SVGT580 960K ...
Страница 32: ...20 IMGT30017EN 3A 1 3 Lifting Frame VII VIII Figure 2A 1 Methods of Unloading and Lifting GT3000 Drives ...
Страница 36: ...Installation GT3000 24 IMGT30017EN 3A 2 1 4 Frames VII VIII Installatiion ...
Страница 58: ...GT3000 Installation 46 IMGT30004EN ...
Страница 107: ...GT3000 Terminal Boards and Power Schematics IMGT30017EN 95 ...
Страница 108: ...Terminal Boards and Power Schematics GT3000 96 IMGT30017EN SVGT200 260 320K J Motor earth connection Field bus ...
Страница 109: ...GT3000 Terminal Boards and Power Schematics IMGT30017EN 97 SVGT390 521K J Field bus Motor earth connection ...
Страница 110: ...Terminal Boards and Power Schematics GT3000 98 IMGT30017EN ...