GT3000
Installation
108 IMGT30017EN
A2.4 MOTOR
CABLE
A2.4.1
Connection cables between inverter and motors
NOTE: The power motor cables must be shielded. If they are not shielded RFI or EMI problems may arise.)
Shielded cables assure a greater immunity of other users of the plant against the noise generated by the drive and they returns high frequency current
directly to the drive through the shielding instead of the current flowing through the motor frame.
The cable shield must be continuous and must be connected to ground at both ends, both to the ground terminal of the motor, and to the cabinet
output terminal, connected at its turn to ground bars.
In general, always foresee the use of a dedicated cable – with minimum section of 50% of the phases – connecting directly the terminal PE of the
drive with the corresponding terminal of the motor. This cable has the function of supplying a preferential way of closure to bring back to the drive the
noises created by the same avoiding to spread them to the plant ground system.
The motor protection connection must be performed locally with the plant ground system.
Motor TB
Figure A2.5.4
Typical connection on the motor
U
V
W
CA B LE
S HIE LD
A2.4.2
Type of cables between inverter and motors
a)
Suggested cable
Symmetrical Shielded cable:
-
3 phase conductors symmetrically arranged
-
single phase non shielded conductors
-
3 PE conductors symmetrically arranged
-
external global shielding for all phase and PE conductors
b)
Suggested cable
Symmetrical shielded cable: as the previous one, but with a single PE conductor
located in the middle of the cable
c)
Suggested cable
Symmetrical shielded cable: shielding with section greater than 50% of the section of
each phase conductor, therefore no further PE conductors are necessary.
d)
Not allowed cable
e)
Not allowed cable
f)
Not allowed cable
Содержание GT3000
Страница 1: ...GT3000 Hardware Software Manual www answerdrives com ...
Страница 2: ......
Страница 4: ......
Страница 8: ...Table Of Contents GT3000 iv IMGT30017EN ...
Страница 12: ...General Safety Precautions viii IMGT30017EN ...
Страница 25: ...GT3000 Technical Data IMGT30017EN 13 Frames IV V VIN SVGT045 166 IP20 ...
Страница 26: ...Technical Data GT3000 14 IMGT30017EN Frames IV V VIN SVGT045 166 IP54 ...
Страница 27: ...GT3000 Technical Data IMGT30017EN 15 Frames IV V IP20 NEMA1 SVGT105 170K J Peso 65Kg Weight 143Lbs ...
Страница 28: ...Technical Data GT3000 16 IMGT30017EN Frames VII VIII IP00 SVGT200 521K SVGT200 470F ...
Страница 29: ...GT3000 Technical Data IMGT30017EN 17 F series Frames 2xVII 2xVIII Parallel IP00 SVGT520 940M ...
Страница 30: ...Technical Data GT3000 18 IMGT30017EN K series Frames 2xVII 2xVIII Parallel IP00 SVGT580 960K ...
Страница 32: ...20 IMGT30017EN 3A 1 3 Lifting Frame VII VIII Figure 2A 1 Methods of Unloading and Lifting GT3000 Drives ...
Страница 36: ...Installation GT3000 24 IMGT30017EN 3A 2 1 4 Frames VII VIII Installatiion ...
Страница 58: ...GT3000 Installation 46 IMGT30004EN ...
Страница 107: ...GT3000 Terminal Boards and Power Schematics IMGT30017EN 95 ...
Страница 108: ...Terminal Boards and Power Schematics GT3000 96 IMGT30017EN SVGT200 260 320K J Motor earth connection Field bus ...
Страница 109: ...GT3000 Terminal Boards and Power Schematics IMGT30017EN 97 SVGT390 521K J Field bus Motor earth connection ...
Страница 110: ...Terminal Boards and Power Schematics GT3000 98 IMGT30017EN ...