Terminal (Program Port/Telnet) Commands
106
NI Series WebConsole & Programming Guide
Terminal Commands (Cont.)
Command
Description
SET IP <D:P:S>
Sets the IP configuration of a specified device.
Enter a Host Name, Type (DHCP or Fixed), IP Address, Subnet Mask,
and Gateway IP Address.
Note
: For NetLinx Central Controllers, the "Host Name" can only
consist of alphanumeric characters.
• Enter Y (yes) to approve/store the information into the Master.
• Enter N (no) to cancel the operation.
Note
:
The Device must be rebooted to enable new settings.
Example:
>SET IP [0:1:0]
--- Enter New Values or just hit Enter to keep current settings ---
Enter Host Name: MLK_INSTRUCTOR
Enter IP type. Type D for DHCP or S for Static IP and then Enter:
DHCP
Enter Gateway IP: 192.168.21.2
You have entered: Host Name MLK_INSTRUCTOR
Type DHCP
Gateway IP 192.168.21.2
Is this correct? Type Y or N and Enter -> y
Settings written. Device must be rebooted to enable new settings.
SET LOG COUNT
Sets the number of entries allowed in the message log.
Note
:
The Master must be rebooted to enable new settings.
Example:
>SET LOG COUNT
Current log count = 1000
Enter new log count (between 50-10000):
Once you enter a value and press the ENTER key, you get the follow-
ing message:
Setting log count to
New log count set, reboot the Master for the
change to take affect.
SET QUEUE SIZE
Provides the capability to modify maximum message queue sizes for
various threads.
Example:
set queue size
This will set the maximum message queue sizes for several threads.
Use caution when adjusting these values.
Set Queue Size Menu:
1. Interpreter (factory default=2000, currently=600)
2. Notification Manager (factory default=2000, currently=200)
3. Connection Manager (factory default=2000, currently=500)
4. Route Manager (factory default=400, currently=200)
5. Device Manager (factory default=500, currently=500)
6. Diagnostic Manager (factory default=500, currently=500)
7. TCP Transmit Threads (factory default=600, currently=200)
8. IP Connection Manager (factory default=800, currently=500)
9. Message Dispatcher (factory default=1000, currently=500)
10. Axlink Transmit (factory default=800, currently=200)
11. PhastLink Transmit (factory default=500, currently=500)
12. ICSNet Transmit (factory default=500, currently=500)
13. ICSP 232 Transmit (factory default=500, currently=500)
14. UDP Transmit (factory default=500, currently=500)
15. NI Device (factory default=500, currently=500)
Enter choice or press ESC.
Содержание NetLinx Master-Ethernet Card/Module NXC-ME260
Страница 8: ...vi NI Series WebConsole Programming Guide Table of Contents ...
Страница 12: ...Overview 4 NI Series WebConsole Programming Guide FIG 1 Internet Explorer with BonJour plug in ...
Страница 13: ...Overview 5 NI Series WebConsole Programming Guide ...
Страница 14: ...Overview 6 NI Series WebConsole Programming Guide ...
Страница 34: ...Onboard WebConsole User Interface 26 NI Series WebConsole Programming Guide ...
Страница 36: ...WebConsole WebControl Options 28 NI Series WebConsole Programming Guide ...
Страница 88: ...WebConsole System Options 80 NI Series WebConsole Programming Guide ...
Страница 104: ...Programming 96 NI Series WebConsole Programming Guide ...
Страница 156: ...Appendix A IPSec Configuration File 148 NI Series WebConsole Programming Guide ...
Страница 161: ...Terminal Program Port Telnet Commands 153 NI Series WebConsole Programming Guide ...