AC Input Power
TM-F2OP-C1XN-01
2-7
AC Input Wire Connection
1. Strip the outside insulation on the AC cable approximately 4 in.
(10 cm). Trim the wires so that the ground wire is 0.5 in. (12 mm)
longer than the other wires. Strip 0.55 in. (14 mm) at the end of each
of the wires. See Figure 2-2 on page 2–8 detail (top).
2. Unscrew the base of the strain relief from the helix-shaped body.
Insert the base through the outside opening in the AC input cover and,
from the inside, screw the locknut securely onto the base.
3. Slide the helix-shaped body onto the AC cable. Insert the stripped
wires through the strain relief base until the outer cable jacket is flush
with the edge of the base. Tighten the body to the base while holding
the cable in place. The cable is now securely fastened inside the strain
relief.
4. Route the AC wires to the input connector terminals as required. For
input connector terminal locations, see lower inset in Figure 2-2
.
To
connect the wiring, loosen the terminal screw, insert the stripped wire
into the terminal, and tighten the screw securely.
5. Route the wires inside the cover to prevent pinching. Fasten the AC
input cover to the unit using the (6-32 x 1 1/4 in. (2)) screws, flat
washers, and lock washers provided. See Figure 2-2.
WARNING: Shock hazard
Ensure that the chassis ground screw does not penetrate more than 3/8 in. (9 mm)
into the rear panel of the unit.
Содержание Sorensen XFR 100-28
Страница 3: ...This page intentionally left blank ii...
Страница 5: ...This page intentionally left blank iv...
Страница 7: ...This page intentionally left blank vi...
Страница 13: ...xii...
Страница 15: ...xiv...
Страница 25: ...1 10...
Страница 67: ...3 18...
Страница 73: ...Remote Operation 4 6 TM F2OP C1XN 01 Figure 4 1 Connecting Programming Sources to J2 Connector...
Страница 75: ...4 8...
Страница 87: ...5 12...