Using Multiple Supplies
TM-F2OP-C1XN-01
3-11
Using Multiple Supplies
You can operate
power supplies of the SAME MODEL with outputs in
series or in parallel to obtain increased load voltage or increased current.
Split supply operation gives you two positive outputs or a positive and a
negative output.
Note:If your application requires the use of isolated programming inputs,
contact the manufacturer about the optional ISOL Interface.
WARNING
There is a shock hazard at the load when using a power supply with a rated
or
combined
output greater than 40 V. To protect personnel against accidental contact
with hazardous voltages created by series connection, ensure that the load,
including connections, has no live parts which are accessible. Also ensure that the
insulation rating of the load wiring and circuitry is greater than or equal to the
maximum
or combined
output voltage of the power supply.
CAUTION
Do not connect power supplies from different manufacturers in parallel or in
series.
CAUTION
The remote programming inputs are internally referenced to the supply’s negative
output. Do not connect remote programming ground lines (J2 terminals 3, 5,
and 7) to the supply’s positive output.
Содержание Sorensen XFR 100-28
Страница 3: ...This page intentionally left blank ii...
Страница 5: ...This page intentionally left blank iv...
Страница 7: ...This page intentionally left blank vi...
Страница 13: ...xii...
Страница 15: ...xiv...
Страница 25: ...1 10...
Страница 67: ...3 18...
Страница 73: ...Remote Operation 4 6 TM F2OP C1XN 01 Figure 4 1 Connecting Programming Sources to J2 Connector...
Страница 75: ...4 8...
Страница 87: ...5 12...