5.46
P
button function
Display:
Pbut
Range:
NONE, Hi, Lo, HiLo, tARE, ZERO
,
P.SEt
Default Value:
NONE
P
button function - a only applicable models with front panel
P
buttons. The
P
button may
be set to operate some of functions also available via the remote input, see
R.INP
below for a
description of these functions. The
P
button is located at the front of 5 or 6 digit LED models and
bargraph models. If both the remote input and
P
button function are operated simultaneously
the
P
button will override the remote input. The functions below are as described in the
R.INP
function below. Functions available are:
NONE, Hi, Lo , HiLo, tARE , ZERO
,
P.SEt
. Note:
To prevent accidental operation of the
P
button in the
tArE
or
ZERO
functions it is necessary
to hold the button in for 2 seconds to perform the selected operation.
5.47
Access mode
Display:
ACCS
Range:
OFF, EASY, NONE
or
ALL
Default Value:
OFF
Access mode - the access mode function
ACCS
has four possible settings namely
OFF, EASY,
NONE
and
ALL
. If set to
OFF
the mode function has no effect on alarm relay operation. If set
to
EASY
the “easy alarm access” mode will be activated. Refer to “Easy alarm relay adjustment
access facility” page
. If set to
NONE
there will be no access to any functions via
FUNC
mode,
entry via
CAL
mode must be made to gain access to alarm and calibration functions. If set to
ALL
then access to all functions, including calibration functions, can be gained via
FUNC
mode.
5.48
Setpoint access mode
Display:
SPAC
Range:
A1, A1-2
etc.
Default Value:
A1
Setpoint access - seen only if more than 1 relay fitted. Sets the access via
FUNC
mode and “easy
alarm access” mode to the alarm relay setpoints. The following choices are available:
A1
- Allows setpoint access to alarm 1 only.
A1-2
- Allows setpoint access to alarms 1 and 2 only.
A1-3
- Allows setpoint access to alarms 1, 2 and 3 etc. up to the maximum number of relays
fitted.
The remote input function (
R.INP
) must be set to
SP.AC
for this function to operate. Note:
Only the setpoints which have been given a value will be accessible e.g. if
A1Hi
is set to
OFF
then there will be no access to the
A1Hi
function when
SPAC
is used.
34 of
PM4COMAN-2.2-1