БЛОК УПРАВЛЕНИЯ CUID-400N
|
БЛОК УПРАВЛІННЯ CUID-400N
|
CONTROL UNIT CUID-400N
51
ADjUSTMENT
Settings
indication
Settings description
Phototest
When set-up is activated, the operation of the closing safety devices is checked (photocells
or photolines), the transmitter of which is connected to output ‘
PH.T
’, and the receiver is
connected to the input ‘
PH1
’ of the control unit module:
—
OFF
. Test is OFF. Photocells connection diagram is shown in
fig.
4.
Default settings.
—
‘direct’ Phototest is ON.
The photocells, connected to the input ‘
PH1
’ (
fig.
5А), are
tested before the closing begins. The operation of the photocells is checked before closing
the door by short-term disconnection and then connection of the power of photocells
transmitter.
—
‘inverse’ Phototest is OFF.
In the case of connection of photo-devices with special
output ‘
TEST
’ in the transmitter (
fig.
5B). Test is OFF.
—‘
inverse’ Phototest is ON.
It is designated for photo-devices with a special output
‘
TEST
’ in the transmitter. The ‘
TEST
’ contact, and contact ‘
−
’ of the
TX
transmitter (
fig.
5B)
are closed for a short period before the control unit starts closing, and the reaction of the
RX
receiver is tested. If the test is failed, the door closing is blocked, and the control unit
module display shows
‘
’.
Operation time
The time of the continuous movement of the door between final positions is set. The
operation time should be sufficient to fully open or close the door (during setup it is
recommended to increase the time by ~ 3 seconds). If the set operation time is less than
the time required for full opening / closing of the door, the movement of the door leaf
stops at the expiration of time:
—2 sec
—3 sec
—4 sec
…—…
—60 sec.
Default settings.
Pause time to automatic closing
Setting pause time to automatic closing. Pause time countdown is activated, if the
automatic mode is selected in the setting
‘
’.
Values without a dot at the end of the value
—activation of a device (e.g., photocells
beam interruption), connected to input ‘
PH1
’, results in the reset of pause time to
automatic closing and the recovery (photocells beam recovery), to the pause time
countdown from the beginning.
Values with a dot at the end of the value
—activation of a device (e.g., photocells beam
interruption), connected to input ‘
PH1
’, results in the reset of pause time to automatic
closing and the recovery (photocells beam recovery), automatic closing in five seconds:
—1 sec
—2 sec
…—…
—5 sec.
Default settings.
…—…
—60 sec