46
ELECTRONIC MODULE
Table
5. Module display indication
Indication
Description
Opening
Closing
Movement stop
Opening stop at the expiration of operating time
Closing stop at the expiration of operating time
Opening final position (opening final position switch is open)
Closing final position (closing final position switch is open)
Intermediate position (final positions switches are closed)
Error in the final positions switches circuit
(final positions switches are open, e.g., if the emergency manual control switch
or a release switch is activated)
Safety device ‘
STOP
’, connected to input ‘
S
’ was activated
Closing safety device, connected to input ‘
PH1
’ was activated
During
PHOTOTEST
damaged or activated safety devices were found (or at least one),
connected to output ‘
PH.T
’
Safety device (optoelectronic sensor /
OSE
), connected to input ‘
SE
’ was activated
Safety device (resistance sensor / 8.2 kOhm), connected to input ‘
SE
’ was activated
Voltage in the output circuit ‘+ 24 V’ is less than 19.2 V
Pause time countdown to automatic closing, when the door is in the open final position
Automatic closing of the door after the pause time countdown
Reset of the pause time to automatic closing, when a closing safety device, connected
to input ‘
PH1
’, was activated
Pause time countdown to automatic closing in the case of pause time reset
Enter operation parameters setting mode
Values saving, when exiting operation parameters setting mode
Safety devices circuits are fault-free
Return to initial settings (default settings)
Invalid command