5
Figure 3. Single Phone Line Burglary Wiring
Trouble
Indication
Cover Tamper
Cover is opened
Power Fail
Input voltage has fallen below 9V
Cell Fail
Cellular communication has a performance failure (i.e. intermittent communication, not operational)
Ethernet Fail
Ethernet communication has a performance failure (i.e. intermittent communication, not
operational)
CS Trouble
Backup communication path to the central station is not operational
CS Fail
Signal transmission to the central station is not operational
Trouble Conditions
The following trouble conditions can be communicated by BAT-Fire to the FACP/burg panel:
•
For UL 1610 installations, refer to Programming section on how to configure BAT-Fire’s PGM3 as
a ringback trigger. A UL-approved siren such as Honeywell Model 747 must be used for ringback.
The ringback feature on the control panel must be disabled.
• For UL 1610 partitioned installations, all partitions must be in the same building and under the
same management. Install the ringback siren where it can be heard by all partitions.