47-00009 • Rev A • 2021-11-19

 Tech Support Line • (888) 88-ALULA • (888) 882-5852

alula.com

FCC NOTICE

This device complies with Part 15 of the FCC rules. Operation is subject 

to the following two conditions:
(1) This device may not cause harmful interference.

(2) This device must accept any interference that may be received, 

including interference that may cause undesired operation.

Changes or modifications not expressly approved by Alula could void the 

user’s authority to operate this equipment.
RF Exposure:
To satisfy FCC RF Exposure requirements for mobile and base station 

transmission devices, a separation distance of 20 cm or more should 

be maintained between the antenna of this device and persons during 

operation. To ensure compliance, operation at closer than this distance is 

not recommended.

Cellular

     FCC ID: XMR2020BG95M1

ISED NOTICE

This device contains licence-exempt transmitter(s)/receiver(s) that comply 
with Innovation, Science and Economic Development Canada’s licence-
exempt RSS(s). Operation is subject to the following two conditions:
(1) This device may not cause interference.
(2) This device must accept any interference, including interference that 
may cause undesired operation of the device.

Cet appareil contient des émetteurs/récepteurs exempts de licence qui 
sont conformes aux RSS exemptés de licence d’Innovation, Sciences et 
Développement économique Canada. L’exploitation est autorisée aux 
deux conditions suivantes:  
(1) L’appareil ne doit pas produire de brouillage.
(2) L’utilisateur de l’appareil doit accepter tout brouillage radioélectrique 
subi, même si le brouillage est susceptible d’en compromettre le 
fonctionnement.

Cellular

     IC: 10224A-2020BG95M1

This Class B digital apparatus complies with Canadian ICES-003. Cet 
appareil numérique de la classe B est conforme à la norme NMB-003 du 
Canada.

TRADEMARKS

Alula, BAT-Fire, and AlulaConnect are trademarks owned by Alula 
Holdings, LLC. AT&T is a trademark of AT&T Intellectual Property II, L.P. 

Verizon is a trademark of Verizon Trademark Services LLC. Taoglas is a 

trademark of Taoglas Group Holdings Limited. Fire-Lite and Honeywell 
are registered trademarks owned by Honeywell International Inc. Unless 

otherwise specified, all trademarks in this manual are protected under 

trademark law. You agree not to copy, use or otherwise infringe upon 
these marks. Alula manuals may also contain other product, service and/or 
company names which may be trademarks of their respective owners.

Physical 

Housing Dimensions
Weight
Mounting Fasteners

Pilot Hole for Screw into Wood
Pilot Hole for Wall Anchor

Cover Securing Screw
Antenna
Wire Gauge Range

8.6 x 5.8 x 2.2 inches [21.8 x 14.6 x 5.5 cm]
13.2 ounces [375 g]
#6 screws and wall anchors [included]
Ø 1/8in [3mm]
Ø 3/16in [4.7mm]
#6 screw [included]
External [included]
24-14AWG

Device Specification

Reported Indications
Current Draw

Compatible Input Voltage Range 
Programmable Output Current Maximum

Cover Tamper

154mA [Standby] 207mA [Max] @ 12VDC                                    

109mA [Standby] 161mA [Max] @ 24VDC
10-28VDC Limited Power
Will shunt up to 75 mA into ground

Environmental

Operating Temperature 
Maximum Humidity

32°F to 120°F [0°C to 48.9°C]
93% non-condensing relative humidity

Models

BAT-FIRE-ATT

BAT-FIRE-VZ

BAT-Fire, AT&T

BAT-Fire, Verizon

Note:

 the only difference between the models is the cellular carrier.

Certification

Safety Standards
Radio
Cellular
California State Fire Marshal
NY Fire Marshal

UL 864 10th edition, ULC-S559, UL 1610, ULC-S304
FCC, IC

AT&T, Verizon

 

 

 

Specifications

Specifications subject to change without notice

Patents Pending

Содержание BAT-Fire AT&T

Страница 1: ...T Fire s DACT phone interface connection provides phone line voltage dial tone ringback tone and all required CID protocol signaling The BAT Fire receives CID events from the FACP burg panel s DACT and then relays the CID events to the central station receiver Point capture The BAT Fire provides inputs that can be used to monitor an FACP s alarm AC fail and trouble points dry contact outputs In th...

Страница 2: ...ation is complete 9 Press the Config button on the BAT Fire for 2 seconds to enable programming Program the BAT Fire via AlulaConnect see Programming section 10 Close the cover Confirm POWER TROUBLE and COMM LEDS are green 11 After installing BAT Fire or modifying any FACP burg panel programming verify proper operation and reporting of all event codes using your FACP burg panel installation manual...

Страница 3: ...ompany lines to the BAT Fire Attention ne connectez pas les lignes de votre compagnie téléphonique au BAT Fire It is recommended to use separate cables for Tip Ring 1 and Tip Ring 2 Failures and Troubles are communicated to FACP burg panel via the BAT Fire dropping voltage to Phone 2 Refer to Programming section on how to configure Phone 2 trouble triggers Stranded wire gauge range 24 14AWG If FAC...

Страница 4: ...2 by Honeywell relay The panel must support the relay contacts as indicated above NC for alarm and AC FAIL and NO for Trouble and battery calculation shall consider the additional current draw into the PGM s during the Normal Standby state Use 4 7k ohm 1 4 Watt minimum resistors not included PGM ports are not supervised Only panels without supervisory signaling can use this setup For UL 864 10th e...

Страница 5: ... not operational CS Fail Signal transmission to the central station is not operational Trouble Conditions The following trouble conditions can be communicated by BAT Fire to the FACP burg panel For UL 1610 installations refer to Programming section on how to configure BAT Fire s PGM3 as a ringback trigger A UL approved siren such as Honeywell Model 747 must be used for ringback The ringback featur...

Страница 6: ...tual interface supervision for both primary and backup Ethernet Remote Programming On site or Remote Enabled or Disabled Disabled Disabled Enabled or Disabled If Disabled Installer must press Config button onsite Phone 2 Trouble Trigger If using Phone Line capture Figure 1 Power Fail Cover Tamper Cell Fail Ethernet Fail CS Fail CS Trouble CS Fail CS Fail Cover Tamper CS Fail Figure 1 Any Enabled T...

Страница 7: ... and backup cellular Sole Path Cell 60 seconds 6 hours 1 hour 180 seconds or shorter 180 seconds or shorter Turn off Ethernet supervision Turn off virtual interface supervision for both primary and backup Ethernet Remote Programming On site or Remote Enabled or Disabled Disabled Enabled or Disabled Enabled or Disabled If Disabled Installer must press Config button onsite Phone 2 Trouble Trigger If...

Страница 8: ...sired output port Select Configure as Output Name output as desired Check all desired trouble triggers Power Fail Cover Tamper Cell Fail Ethernet Fail Central Station Fail Central Station Trouble Select Save Programming BAT Fire central station receiver s Select primary and backup optional receivers Adjust Supervision Interval based on wiring mode 6 hours default complies with UL 864 10th edition ...

Страница 9: ...ware is up to date Device Unused Cellular signal bar LEDs indicate the quality of the cellular connection A minimum of two signal bar LEDs is recommended Number of Signal Bar LEDs Lit Cellular Signal Strength 0 Bad 1 Marginal 2 Acceptable 3 Good 4 Best Operation and Indicator Overview Events are reported to the central station receivers and the Alula platform event system All events use Contact ID...

Страница 10: ... connected 2 Ensure router is powered 3 Ensure UDP ports 1234 and 1235 are open in router modem settings 4 Ensure account is properly configured Cellular LED Off 1 Verify sufficient signal strength for cellular see cellular signal bar table in Operation and Indicator Overview section 2 Ensure account is properly configured Comms LED Yellow 1 Verify the reporting path and ensure the receiver is pro...

Страница 11: ...Collector An output that when engaged shunts current to ground Point A single FACP burg panel output that is either on or off Point Capture The operation mode of BAT Fire connected to the FACP burg panel output s and sensing a trouble or alarm condition Additionally the operation of the FACP burg panel connected to a BAT Fire output and sensing a trouble or communication condition PSTN Public Swit...

Страница 12: ...020BG95M1 This Class B digital apparatus complies with Canadian ICES 003 Cet appareil numérique de la classe B est conforme à la norme NMB 003 du Canada TRADEMARKS Alula BAT Fire and AlulaConnect are trademarks owned by Alula Holdings LLC AT T is a trademark of AT T Intellectual Property II L P Verizon is a trademark of Verizon Trademark Services LLC Taoglas is a trademark of Taoglas Group Holding...